Fuji Electric FRENIC-HVAC User Manual page 132

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Item
Alarm display
(Protective functions)
Alarm history
Monitor
Load factor
Language
Charging lamp
[ 3 ] Function specifications
(1) Terminal functions
Symbol
L1/R, L2/S,
Main circuit power
L3/T
inputs
P(+), N(-)
Converter outputs
G
Grounding
R0, T0
Auxiliary power input
for the control circuit
R1, S1, T1
Synchronous power
input for voltage
detection
R2, T2
Inputs for control
monitoring
[RUN]
Run command
[RST]
Reset alarm command
[X1]
General-purpose
transistor input
[CM]
Digital input common
[PLC]
PLC signal power
AC fuse blown, AC overvoltage, AC undervoltage, AC overcurrent, AC input
current error, input phase loss, synchronous power supply frequency error,
DC fuse blown, DC overvoltage, DC undervoltage, charge circuit fault, heat
sink overheat, external alarm, converter internal overheat, overload, memory
error, keypad communications error, CPU error, network device error,
operation procedure error, A/D converter error, optical network error, IPM
error
Saves and displays the most recent 10 alarms.
Saves and displays the detailed information of the trip cause for the previous
alarm.
Displays input power, input current in RMS, input voltage in RMS, DC link
bus voltage and power supply frequency.
Allows the user to measure the load factor with the keypad.
Allows the user to specify or refer to function codes in any of the three
languages--Japanese, English and Chinese.
Lights when the DC link bus capacitor is charged.
Name
Connects with the three-phase input power lines through a
dedicated reactor.
Connects with the power input terminals P(+) and N(-) on an
inverter.
Grounding terminal for the converter's chassis (or casing).
For a backup of the control circuit power supply, connect the power
lines same as that of the main power input.
Voltage detection terminals for the internal control of the converter.
Connect with the power supply side of the dedicated reactor or
filter.
Detection terminal for AC fuse blown.
Short-circuiting terminals [RUN] and [CM] runs the converter;
opening them stops the converter.
When the converter stops due to an alarm, removing the alarm
factor and short-circuiting the terminals [RST] and [CM] cancels
the protective function, restarting the converter.
0: Enable external alarm trip THR
1: Cancel current limiter
2: 73 answerback
3: Switch current limiter
4: Option DI
Common terminal for digital input signals.
Connects to PLC output signal power supply. (Rated voltage: 24
VDC (22 to 27 VDC)
4-16
Specifications
Functions
LMT-CCL
73ANS
I-LIM
OPT-DI