Note: Entry of a reverse rotation command with the
run command and produces no inverter operation. The rotation direction should be specified
by the data of C21 to C28.
Note: When an pattern operation is commanded via input terminals, the self-hold function of
a run command does not work. Use an alternate switch if necessary.
Note: After completion of a cycle of pattern operation, the inverter decelerates to a stop with
the deceleration time specified by F08 (Deceleration time 1).
C30
Frequency Command 2
For details of frequency command 2, refer to the description of F01.
C31 to C35
Analog Input Adjustment for [12]
C36 to C39
(Offset, Gain, Filter time constant, Gain base point, Polarity)
C41 to C45
Analog Input Adjustment for [C1]
C40
(Offset, Gain, Filter time constant, Gain base point)
Analog Input Adjustment for [V2]
(Offset, Gain, Filter time constant, Gain base point, Polarity)
Terminal [C1] Input Range Selection
Setting up a reference frequency using analog input
You can adjust the gain, polarity, filter time constant, and offset which are applied to analog
inputs (voltage inputs to terminals [12] and [V2], and current input to terminal [C1]).
Adjustable items for analog inputs
Input
terminal
[12]
[C1]
[V2]
Offset (C31, C36, C41)
C31, C36 or C41 configures an offset for an analog voltage/current input. The offset also
applies to signals sent from the external equipment.
- Data setting range: -5.0 to +5.0 (%)
Filter time constant (C33, C38, C43)
C33, C38 or C43 configures a filter time constant for an analog voltage/current input. The
larger the time constant, the slower the response. Specify the proper filter time constant
taking into account the response speed of the machine (load). If the input voltage fluctuates
due to line noises, increase the time constant.
- Data setting range: 0.00 to 5.00 (s)
Gain
Input range
Gain
0 to +10 V,
C32
-10 to +10 V
4 to 20 mA
C37
C42
0 to +10 V,
-10 to +10 V
key or terminal [REV] cancels the
Filter time
Polarity
constant
Base point
C34
C35
C33
C39
C38
C44
C45
C43
6-130
(Refer to F01.)
F01 (Frequency Command 1)
Terminal [C1]
Offset
input range
C31
C36
C40
C41