Nominal
Power
applied
supply
Inverter type
motor
voltage
(HP)
1
FRN001AR1-5U
2
FRN002AR1-5U
3
FRN003AR1-5U
5
FRN005AR1-5U
Three-
7.5 FRN007AR1-5U
phase
10
FRN010AR1-5U
575 V
15
FRN015AR1-5U
20
FRN020AR1-5U
25
FRN025AR1-5U
30
FRN030AR1-5U
Note: A box () replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
3. When used with the inverter, a molded case circuit breaker (MCCB), residual-current-operated
protective device (RCD)/earth leakage circuit breaker (ELCB) or magnetic contactor (MC) should
conform to the EN or IEC standards.
4. When you use a residual-current-operated protective device (RCD)/earth leakage circuit breaker
(ELCB) for protection from electric shock in direct or indirect contact power lines or nodes, be sure
to install type B of RCD/ELCB on the input (primary) of the inverter.
5. The inverter should be used in an environment that does not exceed Pollution Degree 2
requirements.
6. Install the inverter, AC reactor (ACR), input or output filter in an enclosure with minimum degree
of protection of IP2X (Top surface of enclosure shall be minimum IP4X when it can be easily
accessed), to prevent human body from touching directly to live parts of these equipment.
7. Do not connect any copper wire directly to grounding terminals. Use crimp terminals with tin or
equivalent plating to connect them.
8. When you use an inverter at an altitude of more than 6600 ft (2000 m), you should apply basic
insulation for the control circuits of the inverter. The inverter cannot be used at altitudes of more
than 9800 ft (3000 m).
(continue)
Power
Fuse rating
supply
(A)
voltage
3(IEC/EN 60269-2)
4(IEC/EN 60269-2)
6(IEC/EN 60269-2)
10(IEC/EN 60269-2)
Three-
16(IEC/EN 60269-2)
phase
20(IEC/EN 60269-2)
575 V
25(IEC/EN 60269-2)
35(IEC/EN 60269-2)
50(IEC/EN 60269-2)
63(IEC/EN 60269-2)
11-4
Nominal
applied
Inverter type
motor
(HP)
40
FRN040AR1-5U
50
FRN050AR1-5U
60
FRN060AR1-5U
75
FRN075AR1-5U
100
FRN100AR1-5U
125
FRN125AR1-5U
150
FRN150AR1-5U
200
FRN200AR1S-5U
250
FRN250AR1S-5U
300
FRN300AR1S-5U
Fuse rating
(A)
80(IEC/EN 60269-2)
100(IEC/EN 60269-2)
250(IEC 60269-4)
250(IEC 60269-4)
250(IEC 60269-4)
350(IEC 60269-4)
350(IEC 60269-4)
400(IEC 60269-4)
450(IEC 60269-4)
500(IEC 60269-4)