Code
Name
Available in the ROM version 1500 or later.
Data setting range
17 (1017): UP (Increase output frequency)
18 (1018): DOWN (Decrease output frequency)
20 (1020): Cancel PID control
21 (1021): Switch normal/inverse operation
22 (1022): Interlock
24 (1024): Enable communications link via RS-485
or fieldbus
25 (1025): Universal DI
26 (1026): Enable auto search for idling motor
speed at starting
30 (1030): Force to stop
(30 = Active OFF, 1030 = Active ON)
33 (1033): Reset PID integral and differential
components
34 (1034): Hold PID integral component
35 (1035): Select local (keypad) operation
38 (1038): Enable run commands
39:
Protect motor from dew condensation
40:
Enable integrated sequence to switch
to commercial power (50 Hz)
41:
Enable integrated sequence to switch
to commercial power (60 Hz)
58 (1058): Reset UP/DOWN frequency
72 (1072): Count the run time of commercial
power-driven motor 1
81 (1081): Clear all customizable logic timers
87 (1087): Run command 2/1
88:
Run forward 2
89:
Run reverse 2
98:
Run forward
99:
Run reverse
100:
No function assigned
131 (1131): Flowrate switch
132 (1132): Filter clogging reverse rotation command
133 (1133): Switch PID channel
171 (1171): PID multistep command
172 (1172): PID multistep command
181 (1181): External PID multistep command
182 (1182): External PID multistep command
190 (1190): Cancel timer
191 (1191): Enable timer 1
192 (1192): Enable timer 2
193 (1193): Enable timer 3
194 (1194): Enable timer 4
201 (1201): External PID control 1 ON command
202 (1202): Cancel external PID control 1
203 (1203): Switch normal/inverse operation
under external PID control 1
204 (1204): Reset external PID1 integral and
differential components
205 (1205): Hold external PID1 integral component (EPID1-HLD)
211 (1211): External PID control 2 ON command
212 (1212): Cancel external PID control 2
213 (1213): Switch normal/inverse operation
under external PID control 2
214 (1214): Reset external PID2 integral and
differential components
215 (1215): Hold external PID2 integral component (EPID2-HLD)
221 (1221): External PID control 3 ON command
222 (1222): Cancel external PID control 3
223 (1223): Switch normal/inverse operation
under external PID control 3
224 (1224): Reset external PID3 integral and
differential components
225 (1225): Hold external PID3 integral component (EPID3-HLD)
8001:
Auxiliary frequency command 1
8002:
Auxiliary frequency command 2
8003:
PID process command 1
8004:
PID process command 2
6-29
6.2 Function Code Tables
Change
Data
Default
when
copying
setting
running
(UP)
(DOWN)
(Hz/PID)
(IVS)
(IL)
(LE)
(U-DI)
(STM)
(STOP)
(PID-RST)
(PID-HLD)
(LOC)
(RE)
(DWP)
(ISW50)
(ISW60)
(STZ)
(CRUN-M1)
(CLTC)
(FR2/FR1)
(FWD2)
(REV2)
(FWD)
(REV)
(NONE)
(FS)
(FRC)
(PID2/1)
(PID-SS1)
(PID-SS2)
(EPID-SS1)
(EPID-SS2)
(TMC)
(TM1)
(TM2)
(TM3)
(TM4)
(EPID1-ON)
(%/EPID1)
(EPID1-IVS)
(EPID1-RST)
(EPID2-ON)
(%/EPID2)
(EPID2-IVS)
(EPID2-RST)
(EPID3-ON)
(%/EPID3)
(EPID3-IVS)
(EPID3-RST)
Related
page
6-249