K29
Display Filter
K29 specifies a filter time constant to be applied for displaying the output frequency, output
current and other running status on the LCD monitor of the keypad. If the display varies
unstably so as to be hard to read due to load fluctuation or other causes, increase this filter
time constant.
- Data setting range: 0.0 to 5.0 (s)
The display filter can be defined easily in Programming mode as follows.
PRG > 1(Start-up) > 4(Disp Setting) > 10(Disp Filter)
For detailed setting procedure, refer to Chapter 5, Section 5.6.2.4 "Specifying the
running status item to be monitored."
K30
Coefficient for Speed Indication
K30 specifies the coefficient that is used when the load shaft speed is displayed on the LCD
monitor (see K10).
Load shaft speed (r/min) = (K30 Coefficient for speed indication) x (Frequency in Hz)
- Data setting range: 0.01 to 200.00
The coefficient can be specified easily in Programming mode as follows.
PRG > 1(Start-up) > 4(Disp Setting) > 11(Speed Coef)
For detailed setting procedure, refer to Chapter 5, Section 5.6.2.4 "Specifying the
running status item to be monitored."
K31
Display Unit for Input Watt-hour Data
K31 specifies the display unit for input watt-hour (K10 = 35) calculated by the inverter.
The data can be checked by accessing PRG > 3(INV Info) > 4(Maintenance) in Programming
mode.
- Data setting range: 0, 1
Data for K31
0
1
The display unit can be specified easily in Programming mode as follows.
PRG > 1(Start-up) > 4(Disp Setting) > 12(WattHour Unit)
For detailed setting procedure, refer to Chapter 5, Section 5.6.2.4 "Specifying the
running status item to be monitored."
kWh
MWh
6-292