Check Status Of Input/Output Signal - Fuji Electric FRENIC-HVAC User Manual

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

5.6.4.3

Check Status of Input/Output Signal

PRG > 3(INV Info) > 3(I/O Check)
This allows confirmation of the inverter's digital input/output signal and analog input/output signal.
This can be used when confirming operational status during maintenance or on test runs.
Operational
Guide Page
Category
No.
1
Di
2
Di: Link
3
Do
4
Ai/Ao
Fref
0.00
Hz
STOP
Iout
0.00A
PWR
0.03kW
PRG
0.Quick Setup
1.Start-up
2.Function Code
3.INV Info
4.Alarm Info
5.User Config
/
PRG>3
1.Energy Monitor
2.Op Monitor
3.I/O. Check
4.Maintenance
5.Unit Info
/
Table 5.15 "I/O Check" Display Items
Category Details
FWD, REV,
Control circuit
X1-X7,
terminal input signal
EN1, EN2
(terminal input)
FWD, REV,
Communications port
X1-X7,
input signal
XF, XR, RST
Y1-Y4, Y5A,
Output signal
30ABC
12
C1
V2
Analog input signal
FM1-Vo
FM2-Vo
5-69
Code
ON/OFF information on control circuit's
terminal input
(Reversal on short-circuit, no reversal when
open)
Input information on communication-specific
function code S06
(Reversal on 1, no reversal on 0)
Output signal information
Terminal 12 input voltage
Terminal C1 input current
Terminal V2 input voltage
Terminal FM1 output voltage, output current
Terminal FM2 output voltage, output current
Return to previous screen
1. Press the
key while the running mode
screen is displayed.
2. Use the
/
keys to select [3. INV Info],
and confirm with the
3. Use the
/
keys to select [3. I/O
Check], and confirm with the
5.6 Programming Mode
Details
Return to running
key.
key.

Hide quick links:

Advertisement

Table of Contents
loading