Fuji Electric FRENIC-HVAC User Manual page 333

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
J606 External PID Control 2
(Maximum scale) -999.00 to 0.00 to 9990.00
J607
(Minimum scale) -999.00 to 0.00 to 9990.00
J610
J611
I (Integral time) 0.0 to 3600.0 s
J612
D (Differential time) 0.00 to 600.00 s
J613
(Feedback filter) 0.0 to 900.0 s
J614
(Anti-reset wind-up) OFF: Disable
J615
(ON/OFF control hysteresis width) 0.00 to 9990.00
J616
(Proportional operation output convergent
J617
(Proportion cycle) 1 to 150 s
J618
(Upper limit of PID process output) -10 to 110%
J619
(Lower limit of PID process output) -10 to 110%
J620
(Upper and lower limits) 0: Limit PID output with J618,J619
J621
(Alarm output selection) 0: Absolute-value alarm (PV)
J622
(Upper level alarm (AH)) OFF: Disable
J624
(Lower level alarm (AL)) OFF: Disable
J627
(Feedback error detection mode) 0: Disable (Turns ON output signals (EPV2-ERR) and continues
J629
(Feedback error upper-limit) Auto: 105% equivalent
J630
(Feedback error lower-limit) Auto: -5% equivalent
J631
(Feedback error detection time) 0.0 to 300.0 s
J640
(Manual command) 0: Keypad ( /
J651 External PID Control 3
(Mode selection) 0: Disable
*6 The upper and lower level values are restricted by the maximum and minimum scales.
Data setting range
P (Gain) ON/OFF: ON/OFF control
0.000 to 30.000 times
0.01 to 9990.00
*6
*6
0 to 150%
value)
1: 110%, -10% of PID output with J618 exceeded or less than
J619
1: Absolute-value alarm (PV) (with Hold)
2: Absolute-value alarm (PV) (with Latch)
3: Absolute-value alarm (PV) (with Hold and Latch)
4: Deviation alarm (PV)
5: Deviation alarm (PV) (with Hold)
6: Deviation alarm (PV) (with Latch)
7: Deviation alarm (PV) (with Hold and Latch
8: Absolute-value alarm (SV)
9: Absolute-value alarm (SV) (with Hold)
10: Absolute-value alarm (SV) (with Latch)
11: Absolute-value alarm (SV) (with Hold and Latch)
12: Absolute-value alarm (MV)
13: Absolute-value alarm (MV) (with Hold)
14: Absolute-value alarm (MV) (with Latch)
15: Absolute-value alarm (MV) (with Hold and Latch)
-999.00 to 0.00 to 9990.00
*6
-999.00 to 0.00 to 9990.00
*6
operation.)
1: Enable (Free run stop (PVb trip))
2: Enable (Deceleration and stop (PVb trip))
-999.00 to 0.00 to 9990.00
*6
-999.00 to 0.00 to 9990.00
*6
key)
8: Keypad ( /
key) (Balanceless-bumpless)
51: External PID manual command 1(Analog input: Terminals
[12], [C1] and [V2])
52: External PID manual command 2(Analog input: Terminals
[12], [C1] and [V2])
111: Apply external PID control 1 manual command
1: Enable process control (Normal operation)
2: Enable process control (Inverse operation)
11: Enable process control, interlocking with inverter running
(Normal operation)
12: Enable process control, interlocking with inverter running
(Inverse operation)
21: Enable process control by external digital signal (Normal
operation)
22: Enable process control by external digital signal (Inverse
operation)
31: Enable process control by external digital signal, interlocking
with inverter running (Normal operation)
32: Enable process control by external digital signal, interlocking
with inverter running (Inverse operation)
6-23
6.2 Function Code Tables
Change
Data
Default
Related
when
copying
setting
page
running
N
Y
100.00
6-245
N
Y
0.00
Y
Y
0.100
Y
Y
0.0
Y
Y
0.00
Y
Y
0.5
Y
Y
OFF
Y
Y
0.00
Y
Y
0
6-246
Y
Y
30
Y
Y
100
Y
Y
0
Y
Y
0
Y
Y
0
Y
Y
OFF
Y
Y
OFF
Y
Y
0
Y
Y
Auto
Y
Y
Auto
Y
Y
0.1
N
Y
0
N
Y
0