Setting of [Input: Analog]
Calculation circuit (U01, U04, U05, etc)
The following functions can be selected as a calculation circuit.
Furthermore, when upper and lower limit values are the same values, they operate as without
upper and lower limits.
Data for U01
Function
0
No function
2001
Addition
2002
Subtraction
2003
Multiplication
2004
Division
2005
Limiter
2006
Absolute value
2007
Inversion
addition
2051
Comparison 1
2052
Comparison 2
2053
Comparison 3
2054
Comparison 4
2055
Comparison 5
2056
Comparison 6
2071
Window
comparison 1
2072
Window
comparison 2
2101
Maximum
selection
2102
Minimum
selection
2103
Average
2151
Function code
2201
Scale inverse
transformation
2202
Scale
transformation
Description
Output is always 0% (or OFF).
2 inputs 1 output summing circuit
2 inputs 1 output subtraction circuit
2 inputs 1 output multiplication circuit
Division circuit of 2 inputs 1 output
Upper and lower limit limiter circuit of 1
input 1 output
Absolute value circuit of 1 input 1 output
Inversion circuit of 1 input 1 output
Output the comparison of 2 input deviations
digitally.
Output the comparison of 2 input deviations
digitally.
Output the comparison of 2 input deviations
(absolute value) digitally.
Output the comparison of 2 input deviations
(absolute value) digitally.
Output the comparison between 1 input and
1 reference value digitally.
Output the comparison between 1 input and
1 reference value digitally.
Output the comparison between 1 input and
upper/lower threshold value.
Output the comparison between 1 input and
upper/lower threshold value.
Circuit to output the maximum value of 2
inputs.
Circuit to output the minimum value of 2
inputs.
Circuit to output the average of 2 inputs.
The value of function code S13 (%) shall be
input.
Circuit to convert 1 analog input to
0-100.00 with scale set value.
Use this circuit for connection to analog
output terminals. Up to two steps can be
used.
Circuit to convert 0-100.00 of analog 1
input with scale set value.
For input 1, 8000-8085 only are available.
Up to two steps can be used.
6-257
6.3 Details of Function Codes
Such as U04
Such as U05
No object
No object
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Addition value
Addition value
(former clause)
(latter clause)
Deviation
Hysteresis
width
Deviation
Hysteresis
width
Deviation
Hysteresis
width
Deviation
Hysteresis
width
Reference
Hysteresis
value
width
Reference
Hysteresis
value
width
Upper
Lower
threshold value
threshold value
Upper
Lower
threshold value
threshold value
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Maximum
Minimum
scale
scale
Maximum
Minimum
scale
scale
Maximum
Minimum
scale
scale