J550
External PID Multistep Command (Mode selection)
J551
J552
J553
J550, J551, J552 and J553 define an external PID control command as a preset value (3
steps).
 External PID multistep command (Mode selection) (J550)
J550 selects an external PID control under which an external PID multistep command takes
effect.
- Data setting range: 0 bit, 1 bit, 2 bits
Data for J550
0-2 bit = 0
0 bit = 1
1 bit = 1
2 bits = 1
 External PID multistep command (Multistep command 1 to 3) (J551, J552, J553)
J551/J552/J553 specifies a multistep command in a physical quantity.
- Data setting range: -999.00 to 0.00 to 9990.00
• External PID command
EPID-SS2
OFF
OFF
ON
ON
The physical quantity is dependent on the display unit and maximum/minimum scale
specified by the following function codes.
External PID control 1
External PID control 2
External PID control 3
Note: Factory default value is set at J505, J605, J655=0 (according to the PID control 1 feedback
value unit/scale).
(Multistep command 1)
(Multistep command 2)
(Multistep command 3)
Disable multistep command
Enable multistep command under external PID control 1
Enable multistep command under external PID control 2
Enable multistep command under external PID control 3
EPID-SS1
OFF
ON
OFF
ON
Display unit
J505
J605
J655
6-244
Function
Command
Command by J550
J551 (Multistep 1)
J552 (Multistep 2)
J553 (Multistep 3)
Maximum scale
Minimum scale
J506
J606
J656
J507
J607
J657