Function
Name
code
U81
Customizable logic output signal 1
(Function selection)
U82
Customizable logic output signal 2
(Function selection)
U83
Customizable logic output signal 3
(Function selection)
U84
Customizable logic output signal 4
(Function selection)
U85
Customizable logic output signal 5
(Function selection)
U86
Customizable logic output signal 6
(Function selection)
U87
Customizable logic output signal 7
(Function selection)
Data setting range
When step outputs are digital:
0 (1000):
Select multistep
frequency (0 to 1 step)
1 (1001):
Select multistep
frequency (0 to 3 steps)
2 (1002):
Select multistep
frequency (0 to 7 steps)
3 (1003):
Select multistep
frequency (0 to 15 steps)
4 (1004):
Select ACC/DEC time
(2 steps)
5 (1005):
Select ACC/DEC time
(4 steps)
6 (1006):
Enable 3-wire operation
7 (1007):
Coast to a stop
8 (1008):
Reset alarm
9 (1009):
Enable external alarm
trip
(9 = Active OFF/
1009 = Active ON)
11 (1011): Select frequency
command 2/1 Hz2/Hz1
13:
Enable DC braking
14 (1014): Select torque limiter
level 2/1
15:
Switch to commercial
power (50 Hz)
16:
Switch to commercial
power (60 Hz)
17 (1017): UP (Increase output
frequency)
18 (1018): DOWN (Decrease
output frequency)
20 (1020): Cancel PID control
21 (1021): Switch normal/inverse
operation
22 (1022): Interlock
24 (1024): Enable communications
link via RS-485 or
fieldbus
25 (1025): Universal DI
26 (1026): Enable auto search for
idling motor speed at
starting
30 (1030): Force to stop
(30 = Active OFF/
1030 = Active ON)
6-264
Default
setting
100
100
SS1
100
SS2
100
SS4
100
100
SS8
100
RT1
RT2
HLD
BX
RST
THR
DCBRK
TL2/TL1
SW50
SW60
UP
DOWN
Hz/PID
IVS
IL
LE
U-DI
STM
STOP

Hide quick links:

Advertisement

Table of Contents
loading