Example: To detect 0 to 30 kPa with 4 to 20 mA output of the pressure sensor
1) Input monitor
Set E62 (Terminal [C1] extended function) to "20."
2) Scale
- Maximum scale (C65): Set 30.0 to be displayed when the analog input value on
terminal [C1] is 100%.
- Minimum scale (C66): Set 0 to be displayed when the analog input value on terminal
[C1] is 0%.
*The display unit should be selected with C64.
C67
Analog Input Adjustment for Terminal [V2] (Bias value)
C67 specifies a bias value to Reference frequency 2 and analog input monitor terminal [V2].
For details, refer to the description of F01.
C68
Analog Input Adjustment for Terminal [V2] (Bias base point)
C68 specifies a bias base point for Reference frequency 2 and analog input monitor terminal
[V2]. For details, refer to the description of F01.
C70
Analog Input Adjustment for Terminal [V2] (Display unit)
C70 specifies the display unit for analog input monitor, PID control commands and feedback
amounts on terminal [V2].
The specified display unit appears when analog input monitor, SV and PV are displayed on
the main or sub monitor.
Data for
Display unit
C70
1
No display unit
2
%
4
r/min
7
kW
3
20
m
/s (Flowrate)
3
21
m
/min (Flowrate)
3
22
m
/h (Flowrate)
23
L/s (Flowrate)
Data for
Display unit
C70
24
L/min (Flowrate)
25
L/h (Flowrate)
40
Pa (Pressure)
41
kPa (Pressure)
42
MPa (Pressure)
43
mbar (Pressure)
44
bar (Pressure)
45
mmHg (Pressure)
6-135
6.3 Details of Function Codes
(Refer to F01.)
(Refer to F01.)
Data for
Display unit
C70
46
Psi (Pressure)
47
mWG (Pressure)
48
inWG (Pressure)
60
K (Temperature)
61
°C (Temperature)
62
°F (Temperature)
80
ppm (Density)