4.4.3.4

Analog interface card (OPC-AIO)

The analog interface card has the terminals listed below. Mounting this interface card on the
FRENIC-HVAC enables analog input and analog output to/from the inverter.
- One analog voltage input point (0 to ±10 V)
- One analog current input point (4 to 20 mA or 0 to 20 mA, switchable)
- One analog voltage output point (0 to ±10 V)
- One analog current output point (4 to 20 mA)
Ports available for the interface card
This interface card can be connected to any one of the three option connection ports (A-, B-, and
C-ports) on the FRENIC-HVAC.
Terminal functions
Symbol
Power supply
[P10]
for the
potentiometer
Analog voltage
[32]
input
Analog current
[C2]
input
[31]
Analog common
Name
Power supply for frequency command
potentiometer (Variable resistor: 1 to 5 kΩ)
(10 VDC, 10 mA DC max.)
- Used as analog voltage input from external
equipment.
0 to ±10 VDC/0 to ±100% (0 to ±5 VDC/0 to
±100%)
- Signal assignment: Selectable from signals that
can be assigned to inverter standard terminal
[12].
- Resolution: 1/3000
- Used as analog current input from external
equipment.
4 to 20 mA DC/0 to 100%
- Signal assignment: Selectable from signals that
can be assigned to inverter standard terminal
[12].
- Resolution: 1/3000
- Reference terminal for [P10], [32], [C2].
4-57
Functions
4.4 Options
Remarks
Input impedance:
22kΩ
Max. input:
±15 VDC
Input impedance:
250Ω
Max. input:
30 mA DC
Equipotent with
the inverter's
terminal [11]