Fuji Electric FRENIC-HVAC User Manual page 341

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

y codes: Link Functions
Code
Name
y01
RS-485 Communication 1
(Station address)
y02
(Communications error processing) 0: Immediately trip with alarm Er8
y03
y04
y05
(Data length) 0: 8 bits
y06
(Parity check) 0: None (2 stop bits)
y07
y08
(No-response error detection time) OFF: No detection, 1 to 60 s
y09
(Response interval) 0.00 to 1.00 s
y10
(Protocol selection) 0: Modbus RTU protocol
y11
RS-485 Communication 2
(Station address)
y12
(Communications error processing) 0: Immediately trip with alarm ErP
y13
y14
y15
(Data length) 0: 8 bits
y16
(Parity check) 0: None (2 stop bits)
y17
y18
(No-response error detection time) OFF: No detection, 1 to 60 s
y19
(Response interval) 0.00 to 1.00 s
y20
(Protocol selection) 0: Modbus RTU protocol
y60
BACnet Device instance number
y61
y95
Data Clear Processing for Communications
Error
*9
Available at ROM version 2100 or later.
*10 Available at ROM version
2450
or later.
Data setting range
0 to 255
* Set 1 when other than BACnet is 0.
* Set 127 when BACnet is 128 or above.
1: Trip with alarm Er8 after running for the period specified by
timer y03
2: Retry during the period specified by timer y03. If the retry fails,
trip with alarm Er8.
If it succeeds, continue to run.
3: Continue to run
(Timer) 0.0 to 60.0 s
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
6: 76800 bps (Dedicated for BACnet protocol) *10
1: 7 bits
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
(Stop bits) 0: 2 bits
1: 1 bit
1: SX protocol (loader protocol)
2: Fuji general-purpose inverter protocol
3: Metasys N2 protocol
5: BACnet protocol
0 to 255
1: Trip with alarm ErP after running for the period specified by
timer y13
2: Retry during the period specified by timer y13. If the retry fails,
trip with alarm ErP. If it succeeds, continue to run.
3: Continue to run
(Timer) 0.0 to 60.0 s
(Baud rate) 0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
6: 76800 bps (Dedicated for BACnet protocol) *10
1: 7 bits
1: Even parity (1 stop bit)
2: Odd parity (1 stop bit)
3: None (1 stop bit)
(Stop bits) 0: 2 bits
1: 1 bit
1: SX protocol (loader protocol)
2: Fuji general-purpose inverter protocol
3: Metasys N2 protocol
5: BACnet protocol
0 to 4194
(Upper) *9
(Lower) *9 0: Compatible with present version, 128 to 999
0: Do not clear the data of function codes Sxx when a
communications error occurs. (compatible with the
conventional inverters)
1: Clear the data of function codes S01/S05/S19 when a
communications error occurs.
2: Clear the run command assigned bit of function code S06
when a communications error occurs.
3: Clear both data of S01/S05/S19 and run command assigned
bit of S06 when a communications error occurs.
* Related alarms: Er8, ErP, Er4, Er5, ErU
6-31
6.2 Function Code Tables
Change
Data
Default
Related
when
copying
setting
page
running
N
Y
1
6-275
Y
Y
0
Y
Y
2.0
Y
Y
3
Y
Y
0
Y
Y
0
Y
Y
0
Y
Y
OFF
Y
Y
0.01
Y
Y
1
N
Y
1
Y
Y
0
Y
Y
2.0
Y
Y
3
Y
Y
0
Y
Y
0
Y
Y
0
Y
Y
OFF
Y
Y
0.01
Y
Y
0
N
Y
37
6-278
N
Y
0
Y
Y
0