 Screw Specifications (575 V class series)
Nominal
Power
applied
supply
Inverter type
motor
voltage
(HP)
1
FRN001AR1-5U
2
FRN002AR1-5U
3
FRN003AR1-5U
5
FRN005AR1-5U
7.5
FRN007AR1-5U
10
FRN010AR1-5U
15
FRN015AR1-5U
20
FRN020AR1-5U
25
FRN025AR1-5U
Three-
30
FRN030AR1-5U
phase
40
FRN040AR1-5U
575V
50
FRN050AR1-5U
60
FRN060AR1-5U
75
FRN075AR1-5U
100
FRN100AR1-5U
125
FRN125AR1-5U
150
FRN150AR1-5U
200
FRN200AR1S-5U
250
FRN250AR1S-5U
300
FRN300AR1S-5U
Note: A box (
) replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
Main circuit
terminals
Refer
to:
Tightening
Screw
torque
size
(lb-in)
Figure
M4
15.9
A
Figure
M6
51.3
B
Figure
M6
51.3
C
Figure
M8
119.4
D
Figure
M10
238.9
E
Figure
M12
424.7
G
2-30
Aux. control
power supply
Grounding
terminals
Aux. main circuit
power supply
Tightening
Screw
Screw
torque
size
size
(lb-in)
M4
15.9
M6
51.3
M3.5
M6
51.3
M8
119.4
M10
238.9
M10
238.9
Tightening
torque
(lb-in)
10.6