Advertisement

series
USER'S MANUAL
Analog Unit
FEH527d

Advertisement

Table of Contents
loading

Summary of Contents for Fuji Electric NA0AX06-MR

  • Page 1 series USER’S MANUAL Analog Unit FEH527d...
  • Page 2 FEH257 Describes the functions and the operations of SX-Programmer <Reference>, MICREX-SX series Expert. * In addition to the above manuals, the following Fuji Electric Co.,Ltd.site offers various manuals and technical documents associated with MICREX-SX series. URL http://www.fujielectric.com Notes 1. This manual may not be reproduced in whole or part in any form without prior written approval by the manufacturer.
  • Page 3 Safety Precautions Be sure to read the "Safety Precautions" thoroughly before using the module. Here, the safety precautions items are classified into "Warning" and "Caution". Warning : Incorrect handling of the device may result in death or serious injury. Caution : Incorrect handling of the device may result in minor injury or physical damage.
  • Page 4  Do not attempt to change system configurations (such as installing or removing expansion block) while the power is ON, otherwise, failure or erratic operation might occur.  Do not attempt to repair the module by yourself, but contact your Fuji Electric agent, otherwise, fire, accident or failure might occur.
  • Page 5 Revision * The manual No. is printed at the bottom right of the cover of this manual. Printed on * Manual No. Revision contents Jan. 2017 FEH527 First edition May 2017 FEH527a The specifications of the following products were added. •...
  • Page 6: Table Of Contents

    2-2-1 Specification list ............................2-2 2-2-2 Conversion characteristics ..........................2-9 2-3 Names and Functions ........................2-15 2-3-1 Analog input unit (Type: NA0AX06-MR)......................2-15 2-3-2 Analog output unit (Type: NA0AY02-MR) ......................2-17 2-3-3 Analog input/output unit (Type: NA0AW06-MR) ....................2-19 2-3-4 Analog output board (Type: NA3AY02-MR) ....................2-22 2-3-5 Analog input/output board (Type: NA3AW03-MR) ..................2-22...
  • Page 7 Appendix 1-1-1 Handling Upper Cover ........................App.1-1 Appendix 1-1-2 Handling Printed circuit board inside unit ..................App.1-3 Appendix 2 Circuit Isolation Block Diagram Appendix 2-1 Analog Input Unit NA0AX06-MR ..................App.2-1 Appendix 2-2 Analog Output Unit NA0AY02-MR ................App.2-1 Appendix 2-3 Analog Input/Output Unit NA0AW06-MR ..............App.2-2 Appendix 2-4 Thermocouple Input Unit NA0AX02-TC/NA0AX06-TC ..........App.2-2...
  • Page 8: Section 1 Overview

    The SPF series analog unit and temperature measurement unit include the following models. In this manual, these models may be collectively referred to as “analog unit.” Type Specification NA0AX06-MR Analog voltage/current input, 6 channels NA0AY02-MR Analog voltage/current output, 2 channels...
  • Page 9: Analog Signal Range Setting Function

    You can set the parameters of the analog unit by using a program loader. The parameter setting items are as follows: • Analog input unit (Type: NA0AX06-MR): Moving average, resolution • Analog input/output unit (Type: NA0AW06-MR): Moving average, resolution (for analog input only) •...
  • Page 10: Section 2 Specifications

    Section 2 Specifications 2-1 General Specifications Item Specification Remark Physical Operating ambient 0 to +55°C IEC 61131-2 temperature environmental conditions Storage (transportation) -25 to +70°C temperature 20 to 95%RH, no condensation Relative humidity (Transport condition: 5 to 95%RH, no condensation) Pollution degree 2 (Note 1) Corrosion immunity...
  • Page 11: Functional/Performance Specifications

    Section 2 Specifications 2-2 Functional/Performance Specifications 2-2-1 Specification list (1) Analog input unit NA0AX06-MR Item Specification Type NA0AX06-MR No. of input channels 6 channels Input impedance Voltage: 63.2 kW, Current: 250 W Maximum allowable input Voltage: ±15V, Current: ±30mA -10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V...
  • Page 12 Section 2 Specifications (2) Analog output unit NA0AY02-MR Item Specification Type NA0AY02-MR No. of output channels 2 channels External load resistance Voltage output: 500 W to 1 MW, Current output: 0 to 500 W or less Analog output range -10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V -20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA (Collectively set for all channels by the jumper pin in the unit) Resolution...
  • Page 13 Section 2 Specifications (3) Analog input/output unit NA0AW06-MR Item Specification Type NA0AW06-MR No. of input channels 4 channels Input impedance Voltage input: 63.2 kW, Current input: 250 W Maximum allowable input Voltage: ±15V, Current: 30mA -10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V Analog input range -20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA (Collectively set for all channels by the jumper pin in the unit)
  • Page 14 Section 2 Specifications (4) Analog output board, 2 channels NA3AY02-MR Item Specification Type NA3AY02-MR No. of output channels 2 channels External load resistance Voltage output: 1k W to 1MW, Current output: 0 to 500 W or less Analog output range 0 to +10V 0 to 20mA * Selectable by wiring of the terminal block.
  • Page 15 Section 2 Specifications (5) Analog input/output board NA3AW03-MR Item Specification Type NA3AW03-MR No. of input channels 2 channels Input impedance Voltage input: 100 kW, Current input: 125 W Maximum allowable input Voltage: ±15V, Current: 30mA 0 to +10V Analog input range 0 to 20mA * Selectable by wiring of the terminal block.
  • Page 16 Section 2 Specifications (6) Thermocouple input unit NA0AX02-TC/NA0AX06-TC/NA0AX16-TC Item Specification Type NA0AX02-TC NA0AX06-TC NA0AX16-TC No. of input channels 2 channels 6 channels 16 channels Resolution 0.1°C or 1°C *1 Thermocouple type J, K, R, S, E, T, B, N (Collectively set for all channels by the program loader.) Temperature measurement J: -200.0 to 1200.0°C -328.0 to 2192.0°F range...
  • Page 17 Section 2 Specifications (7) Resistance thermometer element input unit NA0AX06-PT Item Specification Type NA0AX06-PT No. of analog input channels 6 channels Resolution 0.1°C or 1°C *1 Applicable resistance thermometer Pt100, Pt1000 (JIS or DIN) element Pt100: -200.0 to 850.0°C (-328.0 to 1562.0°F) Temperature measurement range Pt1000: -200.0 to 600.0°C (-328.0 to 1112.0°F) Overall accuracy...
  • Page 18: Conversion Characteristics

    Section 2 Specifications 2-2-2 Conversion characteristics (1) Analog input 1) 0 to 5V / 0 to 10mA (when set at UNIPOLAR) A/D conversion value (INT type) (4095) 16383 * The value in ( ) is the A/D conversion value when “12 bits” is selected for the resolution. Analog input voltage/current 5V/10mA...
  • Page 19 Section 2 Specifications 4) 0 to 10V / 0 to 20mA (when set at BIPOLAR) A/D conversion value (INT type) 8191 (2047) 0V/0mA Analog input voltage/current 10V/20mA * The values in ( ) are the A/D conversion values when “12 bits” is selected for the resolution. -8192 (-2048) 5) -5 to 5V / -10 to 10mA (when set at UNIPOLAR) A/D conversion value...
  • Page 20 Section 2 Specifications 7) -10 to 10V / -20 to 20mA (when set at UNIPOLAR) A/D conversion value (INT type) (4095) 16383 * The values in ( ) are the A/D conversion values when “12 bits” is selected for the resolution. (2047) 8191 Analog input voltage/current...
  • Page 21 Section 2 Specifications (2) Analog output 1) 0 to 5V / 0 to 10mA (when set at UNIPOLAR) Analog output voltage/current 5V/10mA D/A conversion value (INT type) 16383 2) 0 to 5V / 0 to 10mA (when set at BIPOLAR) Analog output voltage/current 5V/10mA...
  • Page 22 Section 2 Specifications 4) 0 to 10V / 0 to 20mA (when set at BIPOLAR) Analog output voltage/current 10V/20mA 0V/0mA D/A conversion value (INT type) -8192 8191 5) -5 to 5V / -10 to 10mA (when set at UNIPOLAR) Analog output voltage/current 5V/10mA D/A conversion value...
  • Page 23 Section 2 Specifications 7) -10 to 10V / -20 to 20mA (when set at UNIPOLAR) Analog output voltage/current 10V/20mA D/A conversion value -10V/-20mA (INT type) 16383 8) -10 to 10V / -20 to 20mA (when set at BIPOLAR) Analog output voltage/current 10V/20mA -8192...
  • Page 24: Names And Functions

    Section 2 Specifications 2-3 Names and Functions 2-3-1 Analog input unit (Type: NA0AX06-MR) (1) Names The jumper pins in the analog input unit are used to change the analog signal range and digital value range. Therefore, remove the upper cover and control board when setting the jumper pin.
  • Page 25 These are terminals for 24V DC power supply to operate the analog unit and analog input signal. * For the wiring method, see “2-4 Wiring.” NA0AX06-MR 3) JP1: Digital value range selection This jumper pin is used to set the digital value range.
  • Page 26: Analog Output Unit (Type: Na0Ay02-Mr)

    Section 2 Specifications 2-3-2 Analog output unit (Type: NA0AY02-MR) (1) Names The jumper pins in the analog output unit are used to change the analog signal range and digital value range. Therefore, remove the upper cover and control board when setting the jumper pin. 2) Terminal block Expansion connector (OUT) Expansion connector (IN)
  • Page 27 Section 2 Specifications (2) Functions 1) Status indication LED Status indication LED Status Specification PWR of analog output unit ON (red) While 5V DC power is normally supplied. 2) Terminal block These are terminals for 24V DC power supply to operate the analog unit and analog input signal. * For the wiring method, see “2-4 Wiring.”...
  • Page 28: Analog Input/Output Unit (Type: Na0Aw06-Mr)

    Section 2 Specifications 2-3-3 Analog input/output unit (Type: NA0AW06-MR) (1) Names The jumper pins in the analog input/output unit are used to change the analog signal range and digital value range. Therefore, remove the upper cover and control board when setting the jumper pin. 2) Terminal block Expansion connector (OUT) Expansion connector (IN)
  • Page 29 Section 2 Specifications (2) Functions 1) Status indication LED Status indication LED Status Specification PWR of analog input/output unit ON (red) While 5V DC power is normally supplied. 2) Terminal block These are terminals for 24V DC power supply to operate the analog unit and analog input signal. * For the wiring method, see “2-4 Wiring.”...
  • Page 30 Section 2 Specifications 6) JP3 and JP4: Analog input range selection Signal range JP3 setting JP4 setting 0 to 10V 0 to 20mA 0 to 5V 0 to 10mA -10 to 10V -20 to 20mA -5 to 5V -10 to 10mA 7) JP5 to 8: Input voltage/current selection This jumper pin is used to select voltage or current for each channel.
  • Page 31: Analog Output Board (Type: Na3Ay02-Mr)

    Section 2 Specifications 2-3-4 Analog output board (Type: NA3AY02-MR) (1) Names VO0+ IO0+ VO1+ IO1+ 1) Terminal block (2) Functions 1) Terminal block These are terminals for analog output signal. (M2, 5-pole terminal block x 1) Tightening torque: 0.2 N·m * For the wiring method, see “2-4 Wiring.”...
  • Page 32: Thermocouple Input Unit (Type: Na0Ax02-Tc/Na0Ax06-Tc/Na0Ax16-Tc)

    Section 2 Specifications 2-3-6 Thermocouple input unit (Type: NA0AX02-TC/NA0AX06-TC/NA0AX16-TC) (1) Names 2) Terminal block 2) Terminal block Expansion Expansion Expansion Expansion connector (IN) connector (OUT) connector (IN) connector (OUT) Nameplate Nameplate 1) Status indication LED 1) Status indication LED 2) Terminal block NA0AX02-TC NA0AX06-TC 2) Terminal block...
  • Page 33 Section 2 Specifications (2) Functions 1) Status indication LED Status indication LED Status Specification PWR of thermocouple input unit ON (red) While 5V DC power is normally supplied. 2) Terminal block These are terminals for 24V DC power supply to operate the unit and thermocouple input signal. * For the wiring method, see “2-4 Wiring.”...
  • Page 34: Resistance Thermometer Element Input Unit (Type: Na0Ax06-Pt)

    Section 2 Specifications 2-3-7 Resistance thermometer element input unit (Type: NA0AX06-PT) (1) Names 2) Terminal block Expansion connector (OUT) Expansion connector (IN) Nameplate 1) Status indication LED 2) Terminal block (2) Functions 1) Status indication LED Status indication LED Status Specification PWR of resistance thermometer element input unit ON (red)
  • Page 35: Wiring

    Section 2 Specifications 2-4 Wiring 2-4-1 Analog input (1) Target type: NA0AX06-MR/NA0AW06-MR NA0AX06-MR/NA0AW06-MR +15V 24V+ +24V DC External power supply shielded twisted pair cable Analog device (Example of voltage input) shielded twisted pair cable Analog device (Example of current input)
  • Page 36 Section 2 Specifications (2) Target type: NA3AW03-MR NA3AW03-MR For voltage shielded twisted pair cable VI0+ Analog device II0+ (Example of voltage input) VI1+ shielded twisted pair cable For current II1+ Analog device (Example of current input) *1 Unused channels shall basically be short-circuited. (Voltage signal terminal - Current signal terminal - GND) The signal terminal on the unused side of the used channel must be open.
  • Page 37: Analog Output

    Section 2 Specifications 2-4-2 Analog output (1) Target type: NA0AY02-MR and NA0W06-MR NA0AY02-MR/NA0AW06-MR +15V 24V+ +24V DC External power supply shielded twisted pair cable Analog device (Example of voltage output) Analog device Voltage/current selection (Example of current output) *1 Unused channels shall basically be short-circuited. *2 Ground shielded wires at one point on the PLC side (Grounding resistance of 100Ω...
  • Page 38 Section 2 Specifications (2) Target type: NA3AY02-MR and NA0W03-MR NA3AY02-MR/NA3AW03-MR shielded twisted pair cable VO0+ Analog device (Example of voltage output) IO0+ VO1+ shielded twisted pair cable IO1+ Analog device (Example of current output) * Only CH0 for NA3AW03-MR *1 Unused channels shall basically be short-circuited. *2 Ground shielded wires at one point on the PLC side (Grounding resistance of 100Ω...
  • Page 39: Thermocouple Input (Target Type: Na0Ax02-Tc/Na0Ax06-Tc/Na0Ax16-Tc)

    Section 2 Specifications 2-4-3 Thermocouple input (Target type: NA0AX02-TC/NA0AX06-TC/NA0AX16-TC) NA0AX02-TC/NA0AX06-TC/NA0AX16-TC 24V+ +24V DC External power supply TC0+ Thermocouple sensor TC0- TC1+ Thermocouple sensor TC1- TC15+ Thermocouple sensor TC15- Multiplexer * Up to TC1 for NA0AX02-TC Up to TC5 for NA0AX06-TC 2-30...
  • Page 40: Resistance Thermometer Element Input Unit

    Section 2 Specifications 2-4-4 Resistance thermometer element input unit NA0AX06-PT 24V+ +24V DC External power supply Multiplexer *1 When this unit is used under high noise environment, ground grounding terminal (grounding resistance of 100Ω or less). *2 For wiring of Po+, Po-, and COM, use the same length of wires so that the impedance becomes equal. 2-31...
  • Page 41: Dimensions

    Section 2 Specifications 2-5 Dimensions 2-5-1 Expansion unit 1 <Target type> Type Specification NA0AX06-MR Analog voltage/current input, 6 channels NA0AY02-MR Analog voltage/current output, 2 channels NA0AW06-MR Analog voltage/current input/output, Input 4 channels, Output 2 channels NA0AX02-TC Thermocouple input, 2 channels...
  • Page 42: Expansion Unit 2

    Section 2 Specifications 2-5-2 Expansion unit 2 <Target type> Type Specification NA0AX16-TC Thermocouple input, 16 channels Unit: mm 19.5 (97) 2-5-3 Front board <Target type> Type Specification NA3AW03-MR Analog voltage/current input/output, Input 2 channels, Output 1 channel, Front board type NA3AY02-MR Analog voltage/current output, 2 channels, Front board type Unit: mm...
  • Page 43: Section 3 Programming

    Section 3 Programming 3-1 Memory Assignment 3-1-1 Analog input unit NA0AX06-MR WXo.0 CH0 A/D conversion value (INT type) WXo.1 CH1 A/D conversion value (INT type) WXo.2 CH2 A/D conversion value (INT type) WXo.3 CH3 A/D conversion value (INT type) WXo.4 CH4 A/D conversion value (INT type) WXo.5...
  • Page 44: Thermocouple Input Unit Na0Ax02-Tc/Na0Ax06-Tc/Na0Ax16-Tc

    Section 3 Programming 3-1-6 Thermocouple input unit NA0AX02-TC/NA0AX06-TC/NA0AX16-TC (1) NA0AX02-TC WXo.0 T0 Temperature conversion value (INT type) WXo.1 T1 Temperature conversion value (INT type) (2) NA0AX06-TC WXo.0 T0 Temperature conversion value (INT type) WXo.1 T1 Temperature conversion value (INT type) WXo.2 T2 Temperature conversion value (INT type) WXo.3...
  • Page 45: System Definition

    Main unit <How to register units> 1) Open the system definition screen and register the unit that is connected below the main unit (NA0AX06-MR in this example). Right-click here. 2) Right-click the main unit and left-click [Insert]. The “Module insert” dialog box opens.
  • Page 46 Section 3 Programming 3) Right-click the main unit and left-click [Insert]. The “Module insert” dialog box opens. Select “Front Board” for the [Module group type], and “NA3AW03-MR Mixed Analog 3CH” from the [Outline specification] box. Then, click the [OK] button. The unit is registered. The front board is connected on the front of the main unit and registered below the expansion right side unit in the configuration definition tree.
  • Page 47: Setting Parameters

    Section 3 Programming 3-2-2 Setting parameters (1) Analog input unit (Target type: NA0AX06-MR, NA0AW06-MR, NA3AW03-MR) For an analog input unit, set the resolution and moving average execution times. Parameter Setting range Resolution 14 bits, 12 bits, or 14 bits (12 bits) *...
  • Page 48 Section 3 Programming 2) Click the [Parameter] button to display the “Analog Input Unit parameter setting” dialog box. Set the resolution (data format) and moving average for each channel, and then click the [OK] button.
  • Page 49 Section 3 Programming (2) Thermocouple input unit (Target type: NA0AX02-TC, NA0AX06-TC, NA0AX16-TC) For a thermocouple input unit, set the sensor type of the thermocouple, moving average execution times, sampling period, and unit. Parameter Setting range J: -200 to 1200°C K: -200 to 1200°C T: -190 to 380°C E: -190 to 1000°C Sensor type...
  • Page 50 Section 3 Programming (3) Resistance thermometer element input unit (Target type: NA0AX06-PT) For a resistance thermometer element input unit, set the sensor type of the resistance thermometer element, moving average execution times, sampling period, and unit. Parameter Setting range PT100-DIN: PT100-JIS: Sensor type PT1000-DIN:...
  • Page 51: Appendix 1 Unit Handling Procedure

    Appendix 1 Unit Handling Procedure Appendix 1-1 Handling Upper Cover and Printed Circuit board Appendix 1-1-1 Handling Upper Cover (1) How to remove the upper cover 1) Hold the unit with the both hands (with the nameplate facing forward) as shown below. Hold the lower case with the left hand and the upper cover with the right hand.
  • Page 52 Appendix 1 Unit Handling Procedure 3) Pull the upper cover and the lower case of the unit to the right and left. Then, the upper cover is removed from the lower case as shown below. (2) How to mount the upper cover 1) Hold the lower case with the nameplate facing forward and the upper cover with the side having the larger notch up.
  • Page 53: Appendix 1-1-2 Handling Printed Circuit Board Inside Unit

    Appendix 1 Unit Handling Procedure Appendix 1-1-2 Handling Printed circuit board inside unit (1) How to remove the printed circuit board 1) The image below shows the unit with the upper cover removed. 2) The printed board is fixed at the printed board fixing hole of the lower case. 3) Pull the upper part of the lower case rightward and leftward, detach the printed board from the fixing hole, and then, pull it out slowly.
  • Page 54: Appendix 2 Circuit Isolation Block Diagram

    Appendix 2 Circuit Isolation Block Diagram Appendix 2-1 Analog Input Unit NA0AX06-MR Appendix 2-2 Analog Output Unit NA0AY02-MR App.2-1...
  • Page 55: Appendix 2-3 Analog Input/Output Unit Na0Aw06-Mr

    Appendix 2 Circuit Isolation Block Diagram Appendix 2-3 Analog Input/Output Unit NA0AW06-MR Appendix 2-4 Thermocouple Input Unit NA0AX02-TC/NA0AX06-TC App.2-2...
  • Page 56: Appendix 2-5 Thermocouple Input Unit Na0Ax16-Tc

    Appendix 2 Circuit Isolation Block Diagram Appendix 2-5 Thermocouple Input Unit NA0AX16-TC Appendix 2-6 Resistance Thermometer Element Input Unit NA0AX06-PT App.2-3...
  • Page 57 Fuji Electric Co., Ltd. Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan E-mail: micrex-sx@fujielectric.com URL: http://www.fujielectric.com/ Materials covered in this document are subject to revision due to the modification of the product.