Fuji Electric FRENIC-HVAC User Manual page 230

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

The following monitor items appear only when the related PID control or external PID control is
enabled. Items for the PID control and external PID control being disabled cannot be displayed.
Table 5.8 Monitoring Items (Selectable when PID control or external PID control is enabled)
Monitor names
PID command
(Note 2)
PID feedback amount
(Note 2)
PID output
(Note 2)
PID control 1 command
(Note 3)
PID control 1 feedback amount
PID control 2 command
(Note 3)
PID control 2 feedback amount
External PID control 1 command value
(Note 4)
External PID control 1 feedback amount
(Note 4)
External PID control 1 output
External PID control 1 manual command
(Note 5)
External PID control 1 command
External PID control 1 feedback amount
(Note 6)
External PID control 2 command
External PID control 2 feedback amount
(Note 7)
External PID control 2 output
External PID control 2 manual command
(Note 8)
External PID control 3 command
External PID control 3 feedback amount
(Note 9)
External PID control 3 output
External PID control 3 manual command
(Note 10)
Sub-
Unit
monitor
J105
SV
J205
PV
MV
%
SV1
PV1
(Note 3)
SV2
PV2
(Note 3)
E. SVF
E. PVF
E. MV1
(Note 4)
E. MU1
%
E. SV1
%
(Note 6)
E. PV1
E. SV2
%
(Note 7)
E. PV2
E. MV2
(Note 7)
E. MU2
%
E. SV3
%
(Note 9)
E. PV3
E. MV3
(Note 9)
E. MU3
%
5-30
Meaning of displayed value
PID command and its feedback
converted into physical quantities of the
object to be controlled.
The display unit can be selected with
Function code J105 and J205.
PID output in %, assuming the
maximum frequency (F01) as 100%
PID control 1 command and its
feedback converted into physical
quantities of the object to be controlled.
The display unit can be selected with
Function code J105.
PID control 2 command and its
feedback converted into physical
quantities of the object to be controlled.
The display unit can be selected with
Function code J205.
PID output in %, assuming the
maximum frequency (F01) as 100%
The display unit can be selected with
Function code J505.
The display unit can be selected with
Function code J505.
The display unit can be selected with
Function code J605.
The display unit can be selected with
Function code J605.
The display unit can be selected with
Function code J655.
The display unit can be selected with
Function code J655.
Function
code data
for K10
50
51
52
53
54
55
56
60
61
62
63
64
65
70
71
72
73
80
81
82
83

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents