6.3.16 T codes (Timer functions)

T codes configure timer operation.
The timer operation can be configured easily in Programming mode as follows.
PRG > 2(Function Code) > 5(Timer Setup) > 1 to 6(Sub menu #)
For detailed setting procedure, refer to Chapter 5, Section 5.6.3.5 "Configuring Timer Operation."
T01
Timer 1 Operation (Operating mode)
The inverter supports timer operation to run/stop the motor and output digital signals
according to the preset schedule when the real-time clock is enabled, making use of the date
& time information.
It is possible to:
• set the day of the week and start/end times for a maximum of four timers,
• set a maximum of 20 pause dates per year,
• select whether to run the inverter or output external signals for each timer, and
• enable/disable timer operation or cancel timer operation by digital input signals TM1 to
TM4 or TMC, respectively.
Note: To use digital input signals TM1 to TM4 and TMC, it is necessary to assign them to
digital input terminals with E01 to E07 (data = 190 to 194) beforehand.
- Data setting range: 0 to 3
Data for T01
Note: To use digital output signals TMD, TMD1 to TMD4, it is necessary to assign them to
digital output terminals with E20 to E24 and E27 beforehand.
- "In timer operation" signal: TMD (E20 to E24 and E27, data = 190)
- "Timer 1 enabled" signal: TMD1 (E20 to E24 and E27, data = 191)
- "Timer 2 enabled" signal: TMD2 (E20 to E24 and E27, data = 192)
- "Timer 3 enabled" signal: TMD3 (E20 to E24 and E27, data = 193)
- "Timer 4 enabled" signal: TMD4 (E20 to E24 and E27, data = 194)
For details of the setting procedure, refer to Chapter 5, Section 5.6.3.5 "Configuring the
timer operation."
0
Disable
Enable (Inverter run)
1
At the set time, the inverter runs.
(Input of a run command and frequency command is separately required.)
Enable (Digital output signals)
At the set time, the related one of digital output signals TMD, TMD1 to
2
TMD4 comes ON.
(No input of a run command or frequency command is required.)
Enable (Inverter run + Digital output signals)
At the set time, the inverter runs and the related one of digital output
3
signals TMD, TMD1 to TMD4 comes ON.
(Input of a run command and frequency command is separately required.)
T06: Timer 2 Operation (Operating mode)
T11: Timer 3 Operation (Operating mode)
T16: Timer 4 Operation (Operating mode)
Function
6-280