Fuji Electric FRENIC-HVAC User Manual page 131

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

 460 V class series
Item
Type RHC-4C
Applicable inverter
capacity (HP)
Applicable inverter
capacity (kW)
Continuous
capacity (kW)
Overload rating
Voltage 400 V
Required power supply
(kVA)
Carrier frequency
Applicable inverter
capacity (HP)
Applicable inverter
capacity (kW)
Continuous
capacity (kW)
Overload rating
Voltage 400 V
Required power supply
(kVA)
Carrier frequency
Number of phases,
voltage, frequency
Voltage/frequency
fluctuation
(*1) When the power supply voltage is 400 V, 440 V, or 460 V, the output voltage is approximate 640 VDC, 686 VDC, or 710 VDC,
respectively.
(*2) When the power supply voltage is 380 to 398 V/50 Hz and 380 to 430 V/60 Hz, tap-switching is required in the converter. When
the power supply voltage is less than 400 V, it is necessary to decrease the converter capacity.
(*3) Voltage unbalance (%) = (Max. voltage (V) - Min. voltage (V)) / Three-phase average voltage (V) x 67
[2.2] Common specifications
Item
Control method
Running/Stopping
Running status signal
CT/VT switching
Carrier frequency
Input power factor
Restart after momentary power
failure
Power limiting control
(*1) When the power supply voltage is 420 V or above and the converter is running under 50% load or above, the power factor
decreases to about 0.95 (only under regenerative control).
7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 280 315 355 400 500 630
10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 450 475 500 600 800 900
7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 280 315 355 400 500 630
8.8 13 18 22 26 36 44 53 65 88 103 126 150 182 227 247 314 353 400 448 560 705
150% of continuous rating for 1 min
640 to 710 V (Variable with input power voltage)
9.5 14 19 24 29 38 47 57 70 93 111 136 161 196 244 267 341 383 433 488 610 762
15 kHz (typical)
15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 450 475 500 600 800 -
11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 280 315 355 400 500 -
13 18 22 26 36 44 53 65 88 103 126 150 182 227 247 314 353 400 448 560 -
120% of continuous rating for 1 min
640 to 710 V (Variable with input power voltage)
14 19 24 29 38 47 57 70 93 111 136 161 196 244 267 341 383 433 488 610 -
10 kHz (typical)
Three-phase three lines, 380 to 440 V 50 Hz, 380 to 460 V 60 Hz
Voltage: -15 to +10%, Frequency: ±5%, Voltage unbalance: 2% or less
AVR constant control with DC ACR minor
Starts rectification when the converter is powered ON after connection.
Starts boosting when it receives a run signal (terminals [RUN] and [CM]
short-circuited or a run command via the communications link).
After that, the converter is ready to run.
Running, power running, regenerative operation, ready-to-run, alarm output
(for any alarm), etc.
Switching between CT and VT modes.
CT: 150% of overload rating for 1 min
VT: 120% of overload rating for 1 min
(Converters of 500 kW or above are fixed in CT mode.)
Fixed to high carrier frequency
0.99 or above (under 100% load) ( * 1)
Shields the gate when the voltage level reaches the undervoltage level if a
momentary power failure occurs, and the converter can automatically restart
after the power recovers.
Controls the power not to exceed the preset limit value.
4-15
Standard specifications