6.3.4

P codes (Motor 1 parameters)

To use the integrated automatic control functions such as auto torque boost, torque calculation
monitoring, torque limiter, automatic deceleration (anti-regenerative control), auto search for idling
motor speed, slip compensation, and torque vector control, it is necessary to build a motor model in the
inverter by specifying proper motor parameters including the motor capacity and rated current.
P01
Motor 1 (No. of poles)
P01 specifies the number of poles of the motor. Enter the value given on the nameplate of the
motor. This setting is used to display the motor speed on the LCD monitor and to control the
speed (refer to E43). The following expression is used for the conversion.
Motor
- Data setting range: 2 to 22 (poles)
P02
Motor 1 (Rated capacity)
P02 specifies the rated capacity of the motor. Enter the rated value given on the nameplate of
the motor.
Data for P02
0.01 to
1000.00
When accessing P02 with the keypad, take into account that the P02 data automatically
updates data of P03, P06 through P12, and H46.
P03
Motor 1 (Rated current)
P03 specifies the rated current of the motor. Enter the rated value given on the nameplate of
the motor.
- Data setting range: 0.00 to 2000.00 (A)
120
speed
(r/min)
=
No.
of
poles
Unit
kW
When P99 (Motor 1 Selection) = 0 or 4
HP
When P99 (Motor 1 Selection) = 1
6-137
6.3 Details of Function Codes
×
Frequency
(Hz)
Dependency on function code P99