Function code data
Active
Active
ON
OFF
201
1201
External PID control 1 ON command
202
1202
Cancel external PID control 1
Switch normal/inverse operation under
203
1203
external PID control 1
Reset external PID 1 integral and
204
1204
differential components
Hold external PID 1 integral
205
1205
component
211
1211
External PID control 2 ON command
212
1212
Cancel external PID control 2
Switch normal/inverse operation under
213
1213
external PID control 2
Reset external PID 2 integral and
214
1214
differential components
Hold external PID 2 integral
215
1215
component
221
1221
External PID control 3 ON command
222
1222
Cancel external PID control 3
Switch normal/inverse operation under
223
1223
external PID control 3
Reset external PID 3 integral and
224
1224
differential components
Hold external PID 3 integral
225
1225
component
Any negative logic (Active OFF) command cannot be assigned to the functions
marked with "
" in the "Active OFF" column.
The "Enable external alarm trip" (data = 1009) and "Force to stop" (data = 1030) are
fail-safe terminal commands. In the case of "Enable external alarm trip," when data
= 1009, "Active ON" (alarm is triggered when ON); when data = 9, "Active OFF"
(alarm is triggered when OFF).
Terminal commands assigned
6-86
Related
Symbol
function
codes
EPID1-ON
J501
%/EPID1
J501 to J540
EPID1-IVS
EPID1-RST
J501 to J540
EPID1-HLD
EPID2-ON
J601
%/EPID2
J601 to J640
EPID2-IVS
EPID2-RST
J601 to J640
EPID2-HLD
EPID3-ON
J651
%/EPID3
J651 to J690
EPID3-IVS
EPID3-RST
J651 to J690
EPID3-HLD