Fuji Electric FRENIC-HVAC User Manual page 336

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
Data setting range
54 (1054):
In remote operation
55 (1055):
Run command entered
56 (1056):
Motor overheat detected by thermistor
59 (1059):
Terminal [C1] wire break
84 (1084):
Maintenance timer
87(1087):
Frequency arrival signal
95(1095):
Running in fire mode
98 (1098):
Light alarm
99 (1099):
Alarm output (for any alarm)
101(1101):
EN terminal detection circuit error
102(1102):
EN terminal OFF
190 (1190): In timer operation
191 (1191): Timer 1 enabled
192 (1192): Timer 2 enabled
193 (1193): Timer 3 enabled
194 (1194): Timer 4 enabled
200 (1200): Under PID2 control
201 (1201): PID1 alarm
202 (1202): PID1 feedback error
203 (1203): PID2 alarm
204 (1204): PID2 feedback error
211 (1211): Under external PID1 control
212 (1212): External PID1 output
213 (1213): External PID1 output
214 (1214): External PID1 alarm
215 (1215): External PID1 feedback error
221 (1221): Under external PID2 control
222 (1222): External PID2 output
223 (1223): External PID2 output
224 (1224): External PID2 alarm
225 (1225): External PID2 feedback error
231 (1231): Under external PID3 control
232 (1232): External PID3 output
233 (1233): External PID3 output
234 (1234): External PID3 alarm
235 (1235): External PID3 feedback error
2001 (3001): Output of step 1
2002 (3002): Output of step 2
2003 (3003): Output of step 3
2004 (3004): Output of step 4
2005 (3005): Output of step 5
2006 (3006): Output of step 6
2007 (3007): Output of step 7
2008 (3008): Output of step 8
2009 (3009): Output of step 9
2010 (3010): Output of step 10
2011 (3011): Output of step 11
2012 (3012): Output of step 12
2013 (3013): Output of step 13
2014 (3014): Output of step 14
4001 (5001): Terminal [X1] input signal
4002 (5002): Terminal [X2] input signal
4003 (5003): Terminal [X3] input signal
4004 (5004): Terminal [X4] input signal
4005 (5005): Terminal [X5] input signal
4006 (5006): Terminal [X6] input signal
4007 (5007): Terminal [X7] input signal
4010 (5010): Terminal [FWD] input signal
4011 (5011): Terminal [REV] input signal
6000 (7000): Final run command
6001 (7001): Final FWD run command
6002 (7002): Final REV run command
6003 (7003): During acceleration
6004 (7004): During deceleration
6005 (7005): Under anti-regenerative control
6007 (7007): Alarm factor presence
6-26
Change
Data
when
copying
running
(RMT)
(AX2)
(THM)
(C1OFF)
(MNT)
(FARFDT)
(FMRUN)
(L-ALM)
(ALM)
(DECF)
(ENOFF)
(TMD)
(TMD1)
(TMD2)
(TMD3)
(TMD4)
(PID2)
(PV1-ALM)
(PV1-OFF)
(PV2-ALM)
(PV2-OFF)
(EPID1-CTL)
(EPID1-OUT)
(EPID1-RUN)
(EPV1-ALM)
(EPV1-OFF)
(EPID2-CTL)
(EPID2-OUT)
(EPID2-RUN)
(EPV2-ALM)
(EPV2-OFF)
(EPID3-CTL)
(EPID3-OUT)
(EPID3-RUN)
(EPV3-ALM)
(EPV3-OFF
(SO01)
(SO02)
(SO03)
(SO04)
(SO05)
(SO06)
(SO07)
(SO08)
(SO09)
(SO10)
(SO11)
(SO12)
(SO13)
(SO14)
(X1)
(X2)
(X3)
(X4)
(X5)
(X6)
(X7)
(FWD)
(REV)
(FL_RUN)
(FL_FWD)
(FL_REV)
(DACC)
(DDEC)
(REGA)
(ALM_ACT)
Default
Related
setting
page
6-249

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents