Non-linear V/f Patterns 1 and 2 for Voltage (H51 and H53)
H51 or H53 specifies the voltage component at an arbitrary point in the non-linear V/f
pattern.
- Data setting range:
0 to 240 (V)
: Output an AVR-controlled voltage (230 V class series)
0 to 500 (V)
: Output an AVR-controlled voltage (460 V class series)
0 to 690 (V)
: Output an AVR-controlled voltage (575 V class series)
The factory default values for H50 and H51 differ depending on the inverter
capacity and destination. Refer to the following table.
Capacity
H50
H51
Maximum Output Voltage 1 (F06)
F06 specifies the voltage for the maximum frequency 1 (F03).
- Data setting range:
80 to 240 (V) : Output an AVR-controlled voltage (230 V class series)
160 to 500 (V) : Output an AVR-controlled voltage (460 V class series)
200 to 600 (V) : Output an AVR-controlled voltage (575 V class series)
If F05 (Rated Voltage at Base Frequency 1) is set to "OFF," settings of H50 through
H53 and F06 do not take effect. (When the non-linear point is below the base
frequency, the linear V/f pattern applies; when it is above, the output voltage is kept
constant.)
30 HP or below
OFF
230 V class series
460 V class series
575 V class series
0
230 V class series
460 V class series
575 V class series
6-52
40 HP or above
OFF
OFF
OFF
20
0
0