Fuji Electric FRENIC-HVAC User Manual page 314

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
F26
Motor Sound
(Carrier frequency)
F27
F29
Analog Output [FM1]
(Mode selection)
F30
(Voltage adjustment)
F31
Analog Output [FM1]
F32
Pulse Output [FM2]
(Mode selection)
F34
(Voltage adjustment)
F35
F37
Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 1
F40
Torque Limiter 1
F41
F42
Drive Control Selection 1
F43
Current Limiter
(Mode selection)
F44
Data setting range
230 V class series
0.75 to 16 kHz (1 to 25 HP)
0.75 to 10 kHz (30 to 100 HP)
0.75 to 6 kHz (125 HP)
460 V class series
0.75 to 16 kHz (1 to 50 HP)
0.75 to 10 kHz (60 to 125 HP)
0.75 to 6 kHz (150 to 900 HP)
0.75 to 4 kHz (1000 HP)
575 V class series
0.75 to 16 kHz (1 to 50 HP)
0.75 to 10 kHz (60 to 125HP)
0.75 to 6 kHz (150 to 300 HP)
(Tone)
0: Level 0 (Inactive)
1: Level 1
2: Level 2
3: Level 3
0: Output in voltage (0 to 10 VDC)
1: Output in current (4 to 20 mA DC)
2: Output in current (0 to 20 mA DC)
0% to 300%
Select a function to be monitored from the followings.
(Function)
0:
Output frequency 1 (before slip compensation)
1:
Output frequency 2 (after slip compensation)
2:
Output current
3:
Output voltage
4:
Output torque
5:
Load factor
6:
Input power
7:
PID feedback amount
9:
DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration (+)
15: PID command (SV)
16: PID output (MV)
18: Inverter heat sink temperature (200°C/10 V)
20: Reference frequency
50: PID feedback amount 1 (PV1)
51: PID command 1 (SV1)
52: PID deviation 1 (ERR1) (Note 1)
53: PID final deviation (ERR) (Note 1)
54: PID feedback amount 2 (PV2)
55: PID command 2 (SV2)
56: PID deviation 2 (ERR2) (Note 1)
60: External PID feedback amount 1 (EPID1-PV)
61: External PID command 1 (EPID1-SV)
62: External PID deviation 1 (EPID1-ERR) (Note 1)
63: External PID final deviation 1 (EPID-ERR) (Note 1)
65: External PID final output 1 (EPID1-OUT)
70: External PID feedback amount 2 (EPID2-PV)
71: External PID command 2 (EPID2-SV)
72: External PID deviation 2 (EPID2-ERR) (Note 1)
75: External PID final output 2 (EPID2-OUT)
80: External PID feedback amount 3 (EPID3-PV)
81: External PID command 3 (EPID3-SV)
82: External PID deviation 3 (EPID3-ERR) (Note 1)
85: External PID final output 3 (EPID3-OUT)
111: Customizable logic output signal 1
112: Customizable logic output signal 2
113: Customizable logic output signal 3
114: Customizable logic output signal 4
115: Customizable logic output signal 5
116: Customizable logic output signal 6
117: Customizable logic output signal 7
(Note 1) Deviation output is supported only by option terminal
[Ao] (o09).
0: Voltage (0 to +10 VDC)
1: Current (4 to +20 mA DC)
2: Current (0 to +20 mA DC)
0 to 300%
Same as F31.
(Function)
0: Variable torque load
1: Constant torque load
2: Auto torque boost
3: Auto energy saving
(Variable torque load during ACC/DEC)
4: Auto energy saving
(Constant torque load during ACC/DEC)
5: Auto energy saving
(Auto torque boost during ACC/DEC)
OFF: Disable
(Driving)
20% to 150%: Torque limiter level
(Braking)
0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during ACC/DEC)
2: Enable during ACC/constant speed operation
20% to 120% (Assuming the inverter rated current as 100%.)
(Level)
6-4
Change
Data
Default
Related
when
copying
setting
page
running
Y
Y
2
6-70
Y
Y
0
Y
Y
0
6-71
Y*
Y
100
Y
Y
0
Y
Y
0
6-74
Y*
Y
0
Y
Y
0
N
Y
1
6-75
Y
Y
OFF
6-78
N
Y
0
6-80
Y
Y
2
6-82
Y
Y
120