11.1.1

Conformity to the Low Voltage Directive in the EU

If installed according to the guidelines given below, inverters marked with CE are considered as
compliant with the Low Voltage Directive.
Compliance with European Standards
Adjustable speed electrical power drive systems (PDS).
Part 5-1: Safety requirements. Electrical, thermal and energy. IEC/EN 61800-5-1
1. The ground terminal
residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB)* as the
sole method of electric shock protection. Be sure to use ground wires of recommended size listed
Table 11.1.
*With overcurrent protection.
2. To prevent the risk of hazardous accidents that could be caused by damage of the inverter, install
the specified fuses in the supply side (primary side) according to the following tables.
- Breaking capacity: Min. 10 kA
- Rated voltage: Min. 500 V
Nominal
Power
applied
supply
Inverter type
motor
voltage
(HP)
FRN001AR1-2U
1
2
FRN002AR1-2U
FRN003AR1-2U
3
5
FRN005AR1-2U
FRN007AR1-2U
7.5
10
FRN010AR1-2U
15
FRN015AR1-2U
Three-
FRN020AR1-2U 100 (IEC/EN 60269-2)
20
phase
25
FRN025AR1-2U 125 (IEC/EN 60269-2)
230 V
FRN030AR1-2U
30
40
FRN040AR1-2U
FRN050AR1-2U
50
60
FRN060AR1-2U
FRN075AR1S-2U
75
100
FRN100AR1S-2U
FRN125AR1S-2U
125
Note: A box () replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
G should always be connected to the ground. Do not use only a
Power
Fuse rating
supply
(A)
voltage
6 (IEC/EN 60269-2)
10 (IEC/EN 60269-2)
16 (IEC/EN 60269-2)
25 (IEC/EN 60269-2)
35 (IEC/EN 60269-2)
50 (IEC/EN 60269-2)
80 (IEC/EN 60269-2)
250 (IEC60269-4)
350 (IEC60269-4)
Three-
450 (IEC60269-4)
phase
460 V
500 (IEC60269-4)
FRENIC-HVAC
11-3
11.1 欧州規格の適合について
Nominal
applied
Inverter type
motor
(HP)
1
FRN001AR1-4U
2
FRN002AR1-4U
3
FRN003AR1-4U
5
FRN005AR1-4U
7.5 FRN007AR1-4U
10
FRN010AR1-4U
15
FRN015AR1-4U
20
FRN020AR1-4U
25
FRN025AR1-4U
30
FRN030AR1-4U
40
FRN040AR1-4U
50
FRN050AR1-4U
60
FRN060AR1-4U
75
FRN075AR1-4U
100
FRN100AR1-4U
125
FRN125AR1-4U
150
FRN150AR1S-4U
200
FRN200AR1S-4U
250
FRN250AR1S-4U
300
FRN300AR1S-4U
350
FRN350AR1S-4U
450
FRN450AR1S-4U
500
FRN500AR1S-4U
600
FRN600AR1S-4U
800
FRN800AR1S-4U
900
FRN900AR1S-4U
1000
FRN1000AR1S-4U
Fuse rating
(A)
4 (IEC/EN 60269-2)
6 (IEC/EN 60269-2)
10 (IEC/EN 60269-2)
16 (IEC/EN 60269-2)
20 (IEC/EN 60269-2)
25 (IEC/EN 60269-2)
35 (IEC/EN 60269-2)
50 (IEC/EN 60269-2)
63 (IEC/EN 60269-2)
80 (IEC/EN 60269-2)
100 (IEC/EN 60269-2)
125 (IEC/EN 60269-2)
250 (IEC60269-4)
350 (IEC60269-4)
400 (IEC60269-4)
450 (IEC60269-4)
500 (IEC60269-4)
550 (IEC60269-4)
630 (IEC60269-4)
900 (IEC60269-4)
1250 (IEC60269-4)
2000 (IEC60269-4)