C64
Analog Input Adjustment for Terminal [C1] (Display unit)
C64 specifies the display unit for analog input monitor, PID control commands and feedback
amounts on terminal [C1].
The specified display unit appears when analog input monitor, SV and PV are displayed on
the main or sub monitor.
Data for
Display unit
C64
1
No display unit
2
%
4
r/min
7
kW
3
20
m
/s (Flowrate)
3
21
m
/min (Flowrate)
3
22
m
/h (Flowrate)
23
L/s (Flowrate)
Setting up an analog input monitor for terminal [C1]
1) Input monitor
Set E62 (Terminal [C1] extended function) to "20."
2) Display section
Set any of K10 (Main monitor display), K16 (Sub monitor 1 display) and K17 (Sub
monitor 2 display) to "27" (Analog input monitor).
For details, refer to Chapter 5, Section 5.5.1 "Monitoring the running status."
3) Display unit
Select the desired display unit with C64.
4) Scale
- Maximum scale (C65): Set a physical quantity to be displayed when the analog input
value is 100%.
- Minimum scale (C66): Set a physical quantity to be displayed when the analog input
value is 0%.
C65, C66
Analog Input Adjustment for Terminal [C1] (Maximum scale, Minimum scale)
C65 and C66 specify the maximum and minimum scales to display easy-to-understand
physical quantity converted from analog input on terminal [C1].
- Data setting range: -999.00 to 0.00 to 9990.00 for maximum and minimum scales
Data for
Display unit
C64
24
L/min (Flowrate)
25
L/h (Flowrate)
40
Pa (Pressure)
41
kPa (Pressure)
42
MPa (Pressure)
43
mbar (Pressure)
44
bar (Pressure)
45
mmHg (Pressure)
6-134
Data for
Display unit
C64
46
Psi (Pressure)
47
mWG (Pressure)
48
inWG (Pressure)
60
K (Temperature)
61
°C (Temperature)
62
°F (Temperature)
80
ppm (Density)