Table 2.3 Leakage Current of EMC Filter(continue)
Input
Inverter type
power
FRN001AR1-5U
FRN002AR1-5U
FRN003AR1-5U
FRN005AR1-5U
Three-
FRN007AR1-5U
phase
575 V
FRN010AR1-5U
*3
FRN015AR1-5U
FRN020AR1-5U
FRN025AR1-5U
FRN030AR1-5U
*3 Calculated based on these measuring conditions: 575 V/ 60 Hz, neutral grounding in Y-connection,
interphase voltage unbalance ratio 2%.
Note The worst-case conditions include input phase loss.
Leakage current (mA)
Input
Under
Under
power
normal
worst-case
conditions
conditions
68
119
Three-
phase
575 V
34
113
2-40
Inverter type
FRN040AR1-5U
FRN050AR1-5U
FRN060AR1-5U
FRN075AR1-5U
FRN100AR1-5U
FRN125AR1-5U
*3
FRN150AR1-5U
FRN200AR1S-5U
FRN250AR1S-5U
FRN300AR1S-5U
Leakage current (mA)
Under
Under
normal
worst-case
conditions
conditions
56
149
98
375
108
393
18
79