Running/Stopping The Motor; Remote And Local Modes - Fuji Electric FRENIC-HVAC User Manual

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

5.5.3

Running/stopping the motor

By factory default, pressing the
starts running the motor in the forward or
reverse direction and pressing the
decelerates the motor to stop. The
key is enabled only in Running mode.
 Operational relationship between function code F02 (Operation method) and
key
Table 5.11 lists the relationship between function code F02 settings and the
determines the motor rotation direction.
Table 5.11 Motor Rotation Direction Specified by F02
Data for F02
0
In the direction commanded by [FWD] or [REV].
1
(The motor is driven by [FWD] or [REV].)
2
In the forward direction.
3
In the reverse direction.
For the details on operations with function code F02, refer to Chapter 6 "FUNCTION
CODES."
5.5.4

Remote and local modes

The inverter is available in either remote or local mode.
In remote mode, run and frequency commands are selected by function codes. In local mode, the
command source is the keypad, regardless of the settings specified by function codes.
Holding down the
modes.
Switching these modes is also possible by a digital input signal provided from the outside of the
inverter. You need to assign LOC (Select local (keypad) operation) as a digital input signal to any of
terminals [X1] to [X7].
( Refer to E01 through E07.)
The current mode can be checked by the status icons. The
in remote mode and the
Switching from remote to local mode automatically inherits the frequency settings used in remote
mode. If the motor is running at the time of the switching from remote to local, the run command
will be automatically turned ON so that all the necessary data settings will be carried over. If,
however, there is a discrepancy between the settings used in remote mode and ones made on the
keypad (e.g., switching from the reverse rotation in remote mode to the forward rotation only in
local mode), the inverter automatically stops.
/
key
key
/
Pressing
/
runs the motor:
/
keys disabled
key on the keypad for 2 seconds or more switches between remote and local
, in local mode.
LCD monitor
Programming
keys
Program key
RESET key
UP/DOWN/LEFT/RIGHT
arrow key
(Note) The rotational direction of
IEC-compliant motors is opposite to that
of the motor shown here.
5-36
LED indicators
Run key
(forward)
Run key
(reverse)
STOP key
HELP key
SET key
/
key, which
/
/
is displayed
/