<Operation timing scheme>
• In the figure below, normal operation restarts in the 4th retry.
• In the figure below, the inverter fails to restart normal operation within the number of reset
times specified by H04 (in this case, 3 times (H04 = 3)), and issues the alarm output (for any
alarm) ALM.
The auto-reset operation can be monitored from the external equipment by assigning the
digital output signal TRY to any of the programmable, output terminals [Y1] to [Y4],
[Y5A/C], and [30A/B/C] with any of E20 through E24 and E27 (data = 26).
6.3 Details of Function Codes
6-147