E61 to E63
Terminal [12] Extended Function
Terminal [C1] Extended Function
Terminal [V2] Extended Function
E61, E62, and E63 define the function of the terminals [12], [C1], and [V2], respectively.
There is no need to set up these terminals if they are to be used for frequency command
sources.
Data for E61,
E62, or E63
0
1
2
3
4
5
12
13
14
20
30
31
32
33
41
42
43
Input assigned to [12],
[C1] and [V2]:
None
Auxiliary frequency input to be added to the reference
frequency given by frequency command 1 (F01). Will
Auxiliary frequency
not be added to any other reference frequency given
command 1
by frequency command 2 and multistep frequency
commands, etc.
Auxiliary frequency input to be added to all reference
Auxiliary frequency
frequencies given by frequency command 1,
command 2
frequency command 2, multistep frequency
commands, etc.
Inputs command sources such as temperature and
PID process command
pressure under PID control 1 or 2. Function code
1
setting also required: J102/202 = 1
Inputs the second command sources under PID
PID process command
control 1 or 2. Function code setting also required:
2
J102/202 = 1
Inputs feedback amounts such as temperature and
PID feedback value 1
pressure under PID control 1 or 2.
Acceleration/decele-
To be used for making ratio setting by analog input to
ration time ratio setting
acceleration/deceleration time.
Upper limit frequency
To be used for limiting the output frequency by analog
input.
Lower limit frequency
By inputting analog signals from various sensors such
as the temperature sensors in air conditioners to the
inverter, you can monitor the state of external devices
Analog signal input
via the communications link. By using an appropriate
monitor
display coefficient, you can also have various values
to be converted into physical quantities such as
temperature and pressure before they are displayed.
Inputs the 2nd feedback amounts under PID control 1
PID feedback value 2
or 2.
Auxiliary input 1 to
Auxiliary analog input to be added to the process
PID process command
command under PID control 1 or 2.
Auxiliary input 2 to
2nd auxiliary analog input to be added to the process
PID process command
command under PID control 1 or 2.
Flowrate sensor
Input from the flowrate sensor.
Inputs command sources such as temperature and
External PID process
pressure under external PID control 1, 2 or 3. Function
command 1
code setting also required: J502/J602/J652
External PID feedback
Inputs feedback amounts such as temperature and
value 1
pressure under external PID control 1, 2 or 3.
External PID manual
To be used for setting PID output (MV) manually
command 1
when external PID control 1 is canceled.