PRG>4
1.Alarm History
2.Warn. History
3.Retry History
↓
/
PRG>4>1
0.OL1
09:01 AM
0
1.OC1
09:00 AM
1
2.Er4
Oct/19
0
3.Er6
Oct/18
0
4.Err
Oct/18
0
5.Er6
Oct/18
0
↓
/
PRG>4>1>0.OC1[1/9]
Over Current
During ACC
Occurred at
2011/Oct/20,Thu
09:00 AM
↓
/
PRG>4>1>0.OC1[1/9]
Over Current
During ACC
Short Acc time
Excessive load
TB mismatch
Short circuit
↓
/
PRG>4>1>0.OC1[1/9]
Over Current
During ACC
Occurred at
2011/Oct/20,Thu
09:00 AM
↓
PRG>4>1>0.OC1[2/9]
Fref
60.00Hz
Fout1
0.00Hz
Iout
0.00A
Vout
0.0V
Torque
0%
Speed
0
/
PRG>4>1>0.OC1[3/9]
Time
39hour
EneN
16
Edc
580V
T.Int
25
℃
T.Fin
24
℃
Power
24kW
/
3. Use the
←
Most recent alarm
Time triggered
Shows date and time of past alarms
←
4. Use the
5. Shows alarm details.
"---" displayed if no time set
←
6. Use
7. Use the
←
Set frequency
Output frequency
←
Output current
←
Output voltage
←
Calculated torque
←
Speed
←
←
Cumulative run time
←
Number of startups
DC link bus voltage
←
Interior temperature
←
Heat sink temperature
←
Power consumption
←
5-78
/
keys to select [1. Alarm
History], and confirm with the
Number of consecutive alarms
/
keys to select the alarm to
check, and confirm with the
/
to show the alarm factor.
key to confirm the inverter status
at the time the alarm occurred.
key.
key.