4.2

Currents flowing across the inverter terminals

Table 4.1 summarizes average (effective) electric currents flowing across the terminals of each
inverter model for ease of reference when you select peripheral equipment and options.
Power supply
voltage
Three-phase
230 V
Note: A box () replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
Note: The input RMS current values listed in the above table apply when the inverter is connected with a power
supply of 230 V, 60 Hz, Rsce = 120.
If the power supply voltage differs from 230 V, such as 200 V, the input RMS current values will vary in
inverse proportion to the voltage.
Table 4.1 Currents Flowing through Inverter
Nominal applied
motor
Inverter type
(HP)
1
FRN001AR1-2U
2
FRN002AR1-2U
3
FRN003AR1-2U
5
FRN005AR1-2U
7.5
FRN007AR1-2U
10
FRN010AR1-2U
15
FRN015AR1-2U
20
FRN020AR1-2U
25
FRN025AR1-2U
30
FRN030AR1-2U
40
FRN040AR1-2U
50
FRN050AR1-2U
60
FRN060AR1-2U
75
FRN075AR1S-2U
100
FRN100AR1S-2U
125
FRN125AR1S-2U
Input RMS current
(A)
2.8
5.3
7.5
12.9
18.0
24.2
36.0
48.6
60.0
71.5
96.9
121
145
177
246
291
4-2
60 Hz, 230 V
DC link bus current
(A)
3.5
6.5
9.2
15.8
22.1
29.7
44.1
59.6
73.5
87.6
119
149
178
217
302
357