Fuji Electric FRENIC-HVAC User Manual page 317

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
E30
Frequency Arrival
(Hysteresis width) 0.0 to 10.0 Hz
E31
Frequency Detection 1
E32
(Hysteresis width) 0.0 to 120.0 Hz
E34
Overload Early Warning/Current Detection
E35
E37
Current Detection 2
E38
E61
Terminal [12] Extended Function
E62
Terminal [C1] Extended Function
E63
Terminal [V2] Extended Function
E64
Saving of Digital Reference Frequency
E65
Reference Loss Detection
(Continuous running frequency)
E80
Low Torque Detection
Available in the ROM version 1500 or later.
*2 The motor rated current is automatically set. See Table B (function code P03).
*10 Available at ROM version
2450
or later.
Data setting range
111 (1111): Customizable logic output signal 1
112 (1112): Customizable logic output signal 2
113 (1113): Customizable logic output signal 3
114 (1114): Customizable logic output signal 4
115 (1115): Customizable logic output signal 5
116 (1116): Customizable logic output signal 6
117 (1117): Customizable logic output signal 7
190 (1190): In timer operation
191 (1191): Timer 1 enabled
192 (1192): Timer 2 enabled
193 (1193): Timer 3 enabled
194 (1194): Timer 4 enabled
200 (1200): Under PID2 control
201 (1201): PID1 alarm
202 (1202): PID1 feedback error
203 (1203): PID2 alarm
204 (1204): PID2 feedback error
211 (1211): Under external PID1 control
212 (1212): External PID1 output
213 (1213): Running under external PID1
214 (1214): External PID1 alarm
215 (1215): External PID1 feedback error
221 (1221): Under external PID2 control
222 (1222): External PID2 output
223 (1223): Running under external PID2
224 (1224): External PID2 alarm
225 (1225): External PID2 feedback error
231 (1231): Under external PID3 control
232 (1232): External PID3 output
233 (1233): Running under external PID3
234 (1234): External PID3 alarm
235 (1235): External PID3 feedback error
Setting the value in parentheses ( ) shown above assigns a
negative logic output to a terminal. (True if OFF.)
Setting the value of 1000s in parentheses ( ) shown above
assigns a negative logic input to a terminal.
(Level) 0.0 to 120.0 Hz
OFF: Disable
(Level)
1 to 150% of inverter rated current
(Timer) 0.01 to 600.00s
(Level) *10 OFF: Disable
1 to 150% of inverter rated current
(Timer) *10 0.01 to 600.00s
0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID process command 1
4: PID process command 2
5: PID feedback value 1
12: Acceleration/deceleration time ratio setting
13: Upper limit frequency
14: Lower limit frequency
20: Analog signal input monitor
30: PID feedback value 2
31: Auxiliary input 1 to PID process command
32: Auxiliary input 2 to PID process command
33: Flowrate sensor
41: External PID process command 1
42: External PID feedback value 1
43: External PID manual command 1
44: External PID process command 2
45: External PID feedback value 2
46: External PID manual command 2
47: External PID process command 3
48: External PID feedback value 3
49: External PID manual command 3
0: Automatic saving (when main power is turned OFF)
1: Saving by pressing
key
OFF: Cancel
Decel: Decelerate to stop
20% to 120%
(Level) 0% to 150%
6-7
6.2 Function Code Tables
Change
Data
Default
when
copying
setting
running
(CLO1)
(CLO2)
(CLO3)
(CLO4)
(CLO5)
(CLO6)
(CLO7)
(TMD)
(TMD1)
(TMD2)
(TMD3)
(TMD4)
(PID2)
(PV1-ALM)
(PV1-OFF)
(PV2-ALM)
(PV2-OFF)
(EPID1-CTL)
(EPID1-OUT)
(EPID1-RUN)
(EPV1-ALM)
(EPV1-OFF)
(EPID2-CTL)
(EPID2-OUT)
(EPID2-RUN)
(EPV2-ALM)
(EPV2-OFF)
(EPID3-CTL)
(EPID3-OUT)
(EPID3-RUN)
(EPV3-ALM)
(EPV3-OFF)
Y
Y
2.5
60.0
Y
Y
Y
Y
1.0
Y
Y1
*2
Y
Y
10.00
Y
Y1
*2
Y
Y
10.00
N
Y
0
N
Y
0
N
Y
0
Y
Y
1
Y
Y
OFF
Y
Y
20
Related
page
6-106
6-118
6-119
6-121
6-123
6-124