Code
Name
J209
(Tuning manipulated value) 10 to 100% (Maximum frequency = 100%)
J210
J211
I (Integral time) 0.0 to 3600.0 s
J212
D (Differential time) 0.00 to 600.00 s
J213
(Feedback filter) 0.0 to 900.0 s
J214
(Anti-reset wind-up) OFF: Disable
J218
(Upper limit of PID process output) Inherit: Depends on setting of F15
J219
(Lower limit of PID process output) Inherit: Depends on setting of F16
J221 PID Control 2
(Alarm output selection) 0: Absolute-value alarm
J222
(Upper level alarm (AH)) OFF: Disable
J223
(Upper level alarm detection hysteresis
J224
(Lower level alarm (AL)) OFF: Disable
J225
(Upper level alarm detection hysteresis
J227
(Feedback failure detection
(Mode selection))
J228
(Feedback failure continuation duration) Cont.: After detection of the failure, continue to run as specified
J229
(Feedback failure upper-limit) Auto: 105% equivalent
J230
(Feedback failure lower-limit) Auto: -5% equivalent
J231
(Feedback failure detection time) 0.0 to 300.0 s
J249 Slow Flowrate Stop Function
(Mode selection)
*
J250 *
(Operation level) Auto: Adjust automatically
J251 *
(Elapsed time) 0 to 60 s
J256 *
(Initiation inhibition time) 0 to 3600 s
J257 *
(Cancel frequency) OFF: Disable
J258 *
(Cancel deviation level 1) OFF: Disable
J259 *
(Cancel delay timer) 0 to 3600 s
J260 *
(Cancel deviation level 2) OFF: Disable
J249-J260 are available in the ROM version 1600 or later.
*6 The upper and lower level values are restricted by the maximum and minimum scales.
Data setting range
P (Gain) 0.000 to 30.000 times
0.01 to 9990.00
*6
0.0 to 120.0 Hz
0.0 to 120.0 Hz
1: Absolute-value alarm (with Hold)
2: Absolute-value alarm (with Latch)
3: Absolute-value alarm (with Hold and Latch)
4: Deviation alarm
5: Deviation alarm (with Hold)
6: Deviation alarm (with Latch)
7: Deviation alarm (with Hold and Latch)
50: Absolute value alarm (Cancel PID control)
-999 to 0.00 to 9990.00
*6
0.00 to 9990.00
*6
width)
-999 to 0.00 to 9990.00
*6
0.00 to 9990.00
*6
width)
0: Disable (Turns ON output signals (PV2-ERR) and continues
operation.)
1: Enable (Free run stop (PV2 trip))
2: Enable (Deceleration and stop (PV2 trip))
3: Enable (Continuation of operation at the maximum frequency
(upper limit frequency))
4: Enable (Continuation of operation at the minimum frequency
(lower limit frequency))
5: Enable (Continuation of operation at the frequency used when
failure is detected.)
by J227. After stop (output shutoff), cause a PV2 trip.
0 to 3600 s
-999.00 to 0.00 to 9990.00
*6
-999.00 to 0.00 to 9990.00
*6
OFF: Disable
1: Manual operation (stop judgment: MV)
2: Manual operation (stop judgment: PV)
0.00 to 120.00 Hz when J149 = MV
0.00 to 9990.00 when J149 = PV
0.0 to 120.0 Hz
0.01 to 9990.00
*6
0.01 to 9990.00
*6
6-19
6.2 Function Code Tables
Change
when
running
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
*6
Y
Y
Y
Y
Y
Y
Data
Default
Related
copying
setting
page
Y
10%
6-215
Y
0.100
Y
0.0
Y
0.00
Y
0.5
Y
OFF
Y
Inherit
6-216
Y
Inherit
Y
0
Y
OFF
Y
0.00
Y
OFF
Y
0.00
Y
0
Y
Cont.
Y
Auto
Y
Auto
Y
0.1
Y
OFF
Y
Auto
Y
0
Y
0
Y
0.0
Y
OFF
Y
0
Y
OFF