Fuji Electric FRENIC-HVAC User Manual page 700

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

11. Use this inverter at the following power supply system.
Power supply
L1
L2
L3
PEN
TN-C system
Power supply
L1
L2
L3
N
TT system
(Earthed neutral)
200V type inverters can be used at IT or TT system.
Use 400V type inverters at the following IT or TT system.
*1) EMC filter : on
Earthed condition
Non-earthed (isolated from earth) IT system
IT system which earthed neutral by an impedance
Corner earthed / Phase-earthed system by an
impedance or earthed system of 400V(TT system)
*2) EMC filter : off
Earthed condition
Non-earthed (isolated from
earth) IT system
IT system which earthed
neutral by an impedance
Corner earthed /
Phase-earthed system by an
impedance or earthed
system of 400V(TT system)
*1,2)According to chapter 11.1.2.3 of User's manual, turn the EMC filter off.
*3)"product ver." descripted in note Colum, means the alphabet symbol of SER.NO.'s end.
Use 575V type inverters at the following IT or TT system.
Earthed condition
Non-earthed (isolated from earth) IT system
IT system which earthed neutral by an impedance
Corner earthed / Phase-earthed system by an
impedance or earthed system of 575V(TT system)
Inverter
Power supply
L1
L1/R
L2
L2/S
L3
L3/T
N
G
PE
TN-S system
Power supply
Inverter
L1/R
L1
L2/S
L2
L3/T
L3
G
TT system
Available.
In this case the insulation between the control interface and the main circuit of
the inverter is basic insulation. Thus do not connect SELV circuit from
external controller directly (make connection using a supplementary
insulation.)
Use an earth fault detector able to disconnect the power within 5 s after the
earth fault occurs.
Not available.
Can or cannot be used and caution
Available.
Restrict the input voltage at 440V+10%
In this case the insulation between the control interface and
the main circuit of the inverter is basic insulation. Thus do not
connect SELV circuit from external controller directly (make
connection using a supplementary insulation.)
Available.
Restrict the input voltage at 440V+10%
In this case the insulation between the control interface and
the main circuit of the inverter is basic insulation. Thus do not
connect SELV circuit from external controller directly (make
connection using a supplementary insulation.)
Not available.
Available.
In this case the insulation between the control interface and the main circuit of
the inverter is basic insulation. Thus do not connect SELV circuit from
external controller directly (make connection using a supplementary
insulation.)
Use an earth fault detector able to disconnect the power within 5 s after the
earth fault occurs.
Not available.
11-8
Inverter
Power supply
L1/R
L1
L2/S
L2
L3/T
L3
N
G
IT system
Inverter
L1/R
L2/S
L3/T
G
Can or cannot be used and caution
All models of 400V series product.
150HP or bigger models of product
ver. earlier "G" : Use an earth fault
detector able to disconnect the power
within 5 s after the earth fault occurs.
125HP or smaller models of 400V
series product.
150HP or bigger models of product
ver. later "H"
150HP or bigger models of product
ver. earlier "G"
Can or cannot be used and caution
Inverter
L1/R
L2/S
L3/T
G
note *3)