 External PID control 1 to 3 (Feedback error lower-limit) (J529, J629, J679)
J529/J629/J679 specifies the upper limit for feedback errors in a physical quantity.
- Data setting range: -999.00 to 0.00 to 999.00, Auto = 105%
The physical quantity is dependent on the display unit and maximum/minimum scale
specified by the following function codes.
External PID control 1
External PID control 2
External PID control 3
 External PID control 1 to 3 (Feedback error lower-limit) (J530, J630, J680)
J530/J630/J680 specifies the lower limit for feedback errors in a physical quantity. The
physical quantity is dependent on the display unit and maximum/minimum scale specified by
the function codes listed above.
- Data setting range: -999.00 to 0.00 to 999.00, Auto = -5%
 External PID control 1 to 3 (Feedback error detection time) (J531, J631, J681)
J531/J631/J681 specifies the feedback error detection time for the upper-limit
(J529/J629/J679) and lower-limit (J530/J630/J680). If the detection time has elapsed after a
feedback error occurred, the inverter regards it as an error.
- Data setting range: 0 to 300.0 (s)
PV signal
J1-31:
detection timer
J1-29:
upper limit
J1-30:
lower limit
Deceleration
Output frequency
and stop
Fmax:
With J1-27 =
1/2
selected
upper limiter
Fmin:
lower limiter
Free-run stop
With J12-7 = 3 selected
Fmax:
upper limiter
Fmin:
lower limiter
With J12-7 = 4 selected
Fmax:
upper limiter
Fmin:
lower limiter
With J12-7 = 5 selected
Fmax:
upper limiter
Fmin:
lower limiter
PID2 control in
With J12-7 = 6 selected
progress
Fmax:
upper limiter
Fmin:
lower limiter
With J1-27 = 3 to 6 selected, PID1 control is
resumed when PV signals are returned to the
range between the upper and lower limits.
RST input
With J127 = 3 to 6 selected,
ALM output
Display unit
J505
J605
J655
J1-28:
J1-31
operation timer
With J1-27 = 1/2 selected, reset
restoration due to alarm cancel
PID2 control in
progress
RST is valid because
signals are in the range
between the upper and
lower limits.
6-242
Maximum scale
J506
J606
J656
J1-31
ALM = ON
ALM = ON
PV level failure
detection frequency
ALM = ON
ON
ON
Minimum scale
J507
J607
J657
J1-28
PID2 control in progress
RST is invalid because signals
are outside the range between
the upper and lower limits.
ON
ON