Fuji Electric FRENIC-HVAC User Manual page 323

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
H50
Non-linear V/f Pattern 1
(Frequency) OFF: Cancel, 0.1 to 120.0 Hz
H51
H52
Non-linear V/f Pattern 2
(Frequency) OFF: Cancel, 0.1 to 120.0 Hz
H53
H56
Deceleration Time for Forced Stop
H61
Multistep Frequency + UP/DOWN Control
(Initial frequency setting)
H63
Low Limiter
(Mode selection) 0: Limit by F16 (Frequency limiter: Low) and continue to run
H64
(Lower limiting frequency) Inherit: Depends on F16 (Frequency limiter, Low)
H68
Slip Compensation 1
(Operating conditions)
H69
Automatic Deceleration
(Mode selection)
H70
Overload Prevention Control
H71
Deceleration Characteristics
H72
Main Power Down Detection
(Mode selection)
H76
Torque Limiter for Braking
(Frequency increment limit)
H77
Service Life of DC Link Bus Capacitor
(Remaining time)
H78
Maintenance Interval (M1)
H79
Preset Startup Count for Maintenance (M1) OFF: Disable
H80
Output Current Fluctuation Damping Gain
for Motor 1
H89
Reserved *5
H90
Reserved *5
H91
Current Input Wire Break Detection
H92
Continuity of Running
H93
H94
Cumulative Motor Run Time 1
H95
DC Braking
(Braking response mode)
H96
STOP Key Priority/Start Check Function
H97
Clear Alarm Data
H98
Protection/Maintenance Function
(Mode selection)
*5 These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
Data setting range
(Voltage) 0-240 V: Output an AVR-controlled voltage (230 V class series)
0-500 V: Output an AVR-controlled voltage (460 V class series)
0-690 V: Output an AVR-controlled voltage (575 V class series)
(Voltage) 0-240 V: Output an AVR-controlled voltage (230 V class series)
0-500 V: Output an AVR-controlled voltage (460 V class series)
0-690 V: Output an AVR-controlled voltage (575 V class series)
0.00 to 3600 s
1: Last UP/DOWN command value on releasing the run
command
13 to 106: Multistep frequency + UP/DOWN command (Initial
value to be preserved)
1: If the output frequency lowers below the one limited by F16
(Frequency limiter: Low), decelerate to stop the motor.
0.1 to 60.0 Hz
0: Enable during ACC/DEC and at base frequency or above
1: Disable during ACC/DEC and enable at base frequency or
above
2: Enable during ACC/DEC and disable at base frequency or
above
3: Disable during ACC/DEC and at base frequency or above
0: Disable
2: Torque limit control with Force-to-stop if actual deceleration
time exceeds three times the specified one
3: DC link bus voltage control with Force-to-stop if actual
deceleration time exceeds three times the specified one
4: Torque limit control with Force-to-stop disabled
5: DC link bus voltage control with Force-to-stop disabled
OFF: Cancel
Inherit: Follow the selected deceleration time
0.01 to 100.00 Hz/s
0: Disable
1: Enable
0: Disable
1: Enable
0.0 to 120.0 Hz
0 to 43800 (in units of 10 hours)
OFF: Disable
10 to 99990 (in units of 10 hours)
1 to 65535
0.00 to 1.00
0, 1
0, 1
OFF: Disable, 0.1 to 60.0 s
(P) Auto: Adjust automatically
0.000 to 10.000 times
(I) Auto: Adjust automatically
0.010 to 10.000 s
0 to 99990 (The cumulative run time can be modified or reset in
units of 10 hours.)
0: Slow
1: Quick
Data
STOP key priority
0:
Disable
1:
Enable
2:
Disable
3:
Enable
0: Disable
1: Enable (Setting "1" clears alarm data and then returns to "0.")
0 to 255
Bit 0: Lower the carrier frequency automatically
Bit 1: Detect input phase loss
Bit 2: Detect output phase loss
Bit 3: Select life judgment threshold of DC link bus capacitor
(0: Factory default level; 1: User setup level)
Bit 4: Judge the life of DC link bus capacitor
Bit 5: DC fan lock detection
Bit 7: Switch NEMA/UL Type 1, NEMA/UL Type 12 enclosure
(0: NEMA/UL Type 1; 1: NEMA/UL Type 12)
6-13
6.2 Function Code Tables
Change
when
running
N
N
N
N
Y
N
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
Start check function
Y
Disable
Disable
Enable
Enable
Y
Y
(0: Disabled; 1: Enabled)
(0: Disabled; 1: Enabled)
(0: Disabled; 1: Enabled)
(0: Disabled; 1: Enabled)
(0: Disabled; 1: Enabled)
Data
Default
Related
copying
setting
page
Y
OFF
6-159
Y1
0
Y
OFF
Y1
0
Y
20.0
Y
1
6-160
Y
0
6-164
Y
2.0
Y
0
Y
0
Y
OFF
6-165
Y
0
6-166
Y
1
Y
5.0
N
NEMA/UL
6-167
Type 1/12:
43800
N
UL open
type :
87600
N
OFF
6-168
Y
0.20
Y
1
6-169
Y
0
Y
OFF
Y1
Auto
Y1
Auto
N
-
Y
1
Y
3
6-170
N
0
Y
UL open
6-171
type ,
NEMA/UL
Type 1
: 19
NEMA/UL
Type 12
: 147