K03
LCD monitor (Backlight brightness control)
K04
These function codes control the backlight brightness and contrast.
- Data setting range: 0 to 10
Backlight brightness control (K03)
Data for K03
0
Contrast control (K04)
Data for K04
0
The backlight brightness and contrast can be controlled easily in Programming mode as
follows.
PRG > 1(Start-up) > 4(Disp Setting) > 15(Brightness)
PRG > 1(Start-up) > 4(Disp Setting) > 16(Contrast)
For detailed setting procedure, refer to Chapter 5, Section 5.6.2.4 "Specifying the
running status item to be monitored."
K08
LCD Monitor Status Display/Hide Selection
K08 selects whether to display or hide the status messages to be monitored on the LCD
monitor on the keypad.
- Data setting range: 0, 1
Data for K08
0
1
<LCD on the keypad>
(Contrast control)
0, 1, 2, • • • • • • • • • • • • • • • • • 8, 9, 10
Dark
0, 1, 2, • • • • • • • • • • • • • • • • • 8, 9, 10
Light
Hide status messages
Display status messages (factory default)
Status messages
Capacitor lifetime being measured
Undervoltage
No input to EN
No input to RE
Input to BX
Fire mode stopped
In restart mode after momentary power failure
During retry
Rotation direction limited
Running in fire mode
Being driven by commercial power
Dew condensation prevention in operation
Under output limiting
Under overload prevention control
Anti-jam function being activated
Filter clogging prevention
Boost function
In recovery operation from PV level error
Under wet-bulb temperature presumption control
Motor stopped due to slow flowrate
Load factor being measured
6-285
6.3 Details of Function Codes
Light
Dark
Function