Fuji Electric FRENIC-HVAC User Manual page 327

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
J128
(Feedback failure continuation duration) Cont.: After detection of the failure, continue to run as specified
J129
(Feedback failure upper-limit) Auto: 105% equivalent
J130
(Feedback failure lower-limit) Auto: -5% equivalent
J131
(Feedback failure detection time) 0.0 to 300.0 s
J136 PID Multistep Command
(Multistep command 1)
J137
(Multistep command 2)
J138
(Multistep command 3)
J149 Slow Flowrate Stop Function
(Mode selection)
*
J150 *
(Operation level) Auto: Adjust automatically
J151 *
(Elapsed time) 0 to 60 s
J152 *
(Auto-operation frequency lower-limit) 0.0 to 120.0 Hz
J153 *
(Pressurization starting frequency) 0.0 to 120.0 Hz
J154 *
(Pressurizing time) 0 to 60 s
J156 *
(Initiation inhibition time) 0 to 3600 s
J157 *
(Cancel frequency) OFF: Disable
J158 *
`(Cancel deviation level 1) OFF: Disable
J159 *
(Cancel delay timer) 0 to 3600s
J160 *
(Cancel deviation level 2) OFF: Disable
J163 Flowrate Sensor
(Input selection)
*
J164 *
J165 *
J166 *
J188 Filter Clogging Prevention/
Anti Jam Function
(Input selection)
J149-J166 are available in the ROM version 1600 or later.
*6 The upper and lower level values are restricted by the maximum and minimum scales.
Data setting range
by J127. After stop (output shutoff), cause a PV1 trip.
0 to 3600 s
-999.00 to 0.00 to 9990.00
-999.00 to 0.00 to 9990.00
-999.00 to 0.00 to 9990.00
OFF: Disable
1: Manual operation (stop judgment: MV)
2: Manual operation (stop judgment: PV)
11: Auto operation 1 (stop judgment: MV):
Deviation detection method
12: Auto operation 1 (stop judgment: PV):
Deviation detection method
21: Auto operation 2 (stop judgment: MV):
Flowrate sensor detection method
22: Auto operation 2 (stop judgment: PV):
Flowrate sensor detection method
0.00 to 120.00 Hz when J149 = MV
0.00 to 9990.00 when J149 = PV
0.0 to 120.0 Hz
0.01 to 9990.00
*6
0.01 to 9990.00
*6
0: Inherit
Follow analog input selected by E61, E62, and E63.
1: PV1
3
20: m
/s
3
21: m
/min
3
22: m
/h
23: L/s
24: L/min
25: L/h
Note: Data 20 or above is to be used for connection of
customizable logic.
(ON level) OFF: Disable
0.00 to 9990.00
*6
Note: If J163 = 20 or above, no scale can be defined, so the
setting range should be from the minimum to maximum.
(OFF level) OFF: Disable
0.00 to 9990.00
*6
Note: If J163 = 20 or above, no scale can be defined, so the
setting range should be from the minimum to maximum.
(Input filter) 0.00 to 5.00s
0: Disable
1: Enable (Anti jam protection, inverter stop with rLo trip)
2: Enable (Filter clogging trouble, inverter stop with FoL trip)
3: Enable (While warning (filter clogging trouble) is output,
operation is continued.)
6-17
6.2 Function Code Tables
Change
*6
*6
*6
Data
Default
Related
when
copying
setting
page
running
Y
Y
Cont.
6-201
Y
Y
Auto
6-201
Y
Y
Auto
Y
Y
0.1
Y
Y
0.00
Y
Y
0.00
Y
Y
0.00
N
Y
OFF
Y
Y
Auto
Y
Y
0
Y
0.0
Y
Y
0.0
Y
Y
0
Y
Y
0
Y
0.0
Y
Y
OFF
Y
Y
0
Y
Y
OFF
N
Y
0
6-209
Y
Y
OFF
Y
Y
OFF
Y
Y
0.20
Y
Y
0
6-210