E30
Frequency Arrival (Hysteresis width)
E30 specifies the detection level (hysteresis width) for the "Frequency (speed) arrival signal"
FAR.
Output signal
Frequency (speed)
arrival signal
FAR
- Data setting range: 0.0 to 10.0 (Hz)
The operation timings of each signal are as shown below.
Data assigned
to output
Operating condition 1
terminal
Both signals come ON
when the difference
between the output
frequency and the
1
reference frequency
comes within the
frequency arrival
hysteresis width specified
by E30.
6-118
Operating condition 2
FAR always goes OFF when the
run command is OFF or the
reference speed is "0."