Page 1
- この取扱説明書は,インバータが廃棄されるまで大切に保管してください。 - この取扱説明書にはオプションなどの取扱い方は記載されていませんので,それぞれのオプションの取扱 説明書を参照してください。 Thank you for purchasing our FRENIC-HVAC series of inverters. • This product is designed to drive a three-phase induction motor. Read through this manual to become familiar with the handling procedure and correct use. • Improper handling might result in incorrect operation, short life cycle, or failure of this product as well as the motor.
UL 規格およびカナダ規格(cUL 認定)への適合について UL/cUL マーク付きのインバータは, 以下の事項に従って設置することにより, UL 規格およびカナダ規格 (cUL 認定)に適合します。 1. Solid state motor overload protection (motor protection by electronic thermal overload relay) is provided in each model. Use function codes F10 to F12 to set the protection level. モータ過負荷の保護機能があり,保護レベルは機能コード F10~F12 で設定してください。 2.
Page 14
UL 規格およびカナダ規格(cUL 認定)への適合について(続き) 6. All circuits with terminals L1/R, L2/S, L3/T, R0, T0, R1, T1 must have a common disconnect and be connected to the same pole of the disconnect if the terminals are connected to the power supply. Terminals R0, T0 must be protected by Class J Fuses or a Circuit Breakers for all capacity in the figure below.
Page 15
UL 規格およびカナダ規格(cUL 認定)への適合について(続き) Plenum rated drives(プレナム定格) UL Enclosed Type is suitable for installation in a compartment handling conditioned air. UL エンクロージャタイプの製品は,空調区画に設置することができます。 10. Mounting the wiring plate (配線プレート) To use products intended for Europe as UL compliant products, attach a separate conduit plate.. 欧州向をUL適合品として使用するには,別途コンジットプレートを取り付けてください。...
Page 16
UL 規格およびカナダ規格(cUL 認定)への適合について(続き) 12. Install UL certified fuses or circuit breaker between the power supply and the inverter, referring to the table below. 下表を参照の上,電源とインバータの間に UL 認定品のヒューズまたはブレーカを設置してください。 Required torque 締付けトルク lb-in(N・m) Inverter type Aux. control Main Control Aux. main インバータ形式 power supply power supply terminal circuit...
Page 17
UL 規格およびカナダ規格(cUL 認定)への適合について(続き) Wire size 電線サイズ AWG(mm ) Main terminal 主回路 Cu Wire 銅電線 L1/R,L2/S,L3/T U,V,W Inverter type インバータ形式 75℃電線 75℃電線 0.75 FRN0.75AR1L-2J FRN1.5AR1L-2J 14(2.1) 14(2.1) FRN2.2AR1L-2J 12(3.3) FRN3.7AR1L-2J FRN5.5AR1L-2J 10(5.3) 10(5.3) FRN7.5AR1L-2J 8(8.4) FRN11AR1L-2J 8(8.4) F R N 1 5 A R 1 L - 2 J 6(13.3) 6(13.3) 1 8 .
Preface Thank you for purchasing our FRENIC-HVAC series of inverters. This product is designed to drive a three-phase induction motor. This instruction manual provides only minimum requisite information for wiring and operation of the product. Read through this manual before use.
Page 62
AC power supply to which the product is to be connected. • When using this product in combination with a PWM converter, refer to the instructions given in the FRENIC-HVAC User's Manual. Otherwise, a fire or an accident could occur.
Page 63
• In general, sheaths of the control signal wires are not specifically designed to withstand a high voltage (i.e., reinforced insulation is not applied). Therefore, if a control signal wire comes into direct contact with a live conductor of the main circuit, the insulation of the sheath might break down, which would expose the signal wire to a high voltage of the main circuit.
Page 64
Design the machinery or equipment so that human safety is ensured after restarting. • If the user configures the function codes wrongly without completely understanding this Instruction Manual and the FRENIC-HVAC User's Manual, the motor may rotate with a torque or at a speed not permitted for the machine.
Page 65
Maintenance and inspection, and parts replacement • Before proceeding to maintenance or inspection, turn OFF the power and wait at least 10 minutes. Make sure that the charging lamp is turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below).
Conformity to the Low Voltage Directive in the EU If installed according to the guidelines given below, inverters marked with CE are considered as compliant with the Low Voltage Directive 2006/95/EC. Compliance with European Standards Adjustable speed electrical power drive systems (PDS). Part 5-1: Safety requirements.
Page 67
Conformity to the Low Voltage Directive in the EU (Continued) ■HP rating Fuse rating Fuse rating Inverter type Inverter type FRN001AR1 -2U 6(IEC/EN 60269-2) FRN001AR1 -4U 4(IEC/EN 60269-2) FRN002AR1 -2U 10(IEC/EN 60269-2) FRN002AR1 -4U 6(IEC/EN 60269-2) FRN003AR1 -2U 16(IEC/EN 60269-2) FRN003AR1 -4U 10(IEC/EN 60269-2) FRN005AR1 -2U...
Page 68
Conformity to the Low Voltage Directive in the EU (Continued) 9. Use wires listed in IEC 60364-5-52. ■kW rating Recommended wire size (mm Main terminal Aux. DC reactor Aux main control Main power input Inverter Inverter type connection Control power power outputs [L1/R,...
Page 69
Conformity to the Low Voltage Directive in the EU (Continued) ■HP rating Recommended wire size (mm Main terminal Aux. DC reactor Aux main control Main power input Inverter Inverter type connection Control power power outputs Inverter’s [L1/R, [P1, P(+)] circuit supply supply [U, V, W]...
Page 70
Conformity to the Low Voltage Directive in the EU (Continued) 10. The inverter has been tested with IEC/EN 61800-5-1 2007 Short-circuit Test under the following conditions. Short-circuit current in the supply: 10,000 A 240V or below (200V class series inverters of 18.5 kW (25HP) or below.) 230V or below (230V class series inverters of 22 kW (30HP) or above.) 480V or below (480V class series inverters) 11.
Conformity with UL standards and CSA standards (cUL-listed for Canada) UL/cUL-listed inverters are subject to the regulations set forth by the UL standards and CSA standards (cUL-listed for Canada) by installation within precautions listed below. 1. Solid state motor overload protection (motor protection by electronic thermal overload relay) is provided in each model.
Page 72
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) 8. UL enclosure type UL enclosed type formats are shown in the table below. Enclosure Type Type Open Type FRN_ _ _AR1S-□□ Type 1 FRN_ _ _AR1U-□□ FRN_ _ _AR1M-□□ FRN_ _ _AR1L-□□...
Page 73
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) 12. Install UL certified fuses or circuit breaker between the power supply and the inverter, referring to the table below. ■kW rating Required torque lb-in(N・m) Inverter type Main Control Aux.
Page 74
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) Required torque lb-in(N・m) Inverter type Main Control Aux. control Aux. main terminal circuit power supply power supply 0.75 FRN0.75AR1 -4 FRN1.5AR1 -4 FRN2.2AR1 -4 15.9 FRN3.7AR1 -4 (1.8) (4.0) FRN4.0AR1 -4E FRN5.5AR1 -4 FRN7.5AR1 -4...
Page 75
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) Wire size AWG (mm Main terminal Cu wire L1/R,L2/S,L3/T U,V,W Inverter type 75°C 75°C wire wire 0.75 FRN0.75AR1 -2 14(2.1)*1 FRN1.5AR1 -2 14(2.1) *1 FRN2.2AR1 -2 FRN3.7AR1 -2 12(3.3)*1 (4.0) FRN4.0AR1 -2E 10(5.3)*1...
Page 76
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) Wire size AWG (mm Main terminal L1/R,L2/S,L3/T U,V,W Inverter type 75°C 75°C wire wire 0.75 FRN0.75AR1 -4 FRN1.5AR1 -4 FRN2.2AR1 -4 14 (2.1) *1 14 (2.1) *1 FRN3.7AR1 -4 (4.0) * FRN4.0AR1 -4E FRN5.5AR1 -4...
Page 77
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) ■HP rating Required torque lb-in(N・m) Inverter type Main Control Aux. control Aux. main terminal circuit power supply power supply FRN001AR1 -2U FRN002AR1 -2U 15.9 (1.8) FRN003AR1 -2U FRN005AR1 -2U FRN007AR1 -2U FRN010AR1 -2U 51.3...
Page 78
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) Required torque lb-in(N・m) Inverter type Main Control Aux. control Aux. main terminal circuit power supply power supply FRN001AR1 -4U FRN002AR1 -4U FRN003AR1 -4U 15.9 (1.8) FRN005AR1 -4U FRN007AR1 -4U FRN010AR1 -4U FRN015AR1 -4U FRN020AR1 -4U...
Page 79
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) Wire size AWG (mm Main terminal Cu wire L1/R,L2/S,L3/T U,V,W Inverter type 75°C 75°C wire wire FRN001AR1 -2U FRN002AR1 -2U 14(2.1)*1 14 (2.1) *1 FRN003AR1 -2U FRN005AR1 -2U 12(3.3)*1 10(5.3)*1 FRN007AR1 -2U 10 (5.3) *1...
Page 80
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued) Wire size AWG (mm Main terminal L1/R,L2/S,L3/T U,V,W Inverter type 75°C 75°C wire wire FRN001AR1 -4U FRN002AR1 -4U FRN003AR1 -4U 14 (2.1) *1 14 (2.1) *1 FRN005AR1 -4U FRN007AR1 -4U 12 (3.3) *1 FRN010AR1 -4U FRN015AR1 -4U...
Page 81
8.4.3 Compliance with IEC/EN 61000-3-12 .... 8-4 8.5 Compliance with UL Standards and Canadian Standards (cUL certification)........8-4 8.5.1 General ............8-4 8.5.2 Considerations when using FRENIC-HVAC in systems to be certified by UL and cUL ..8-4 Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
If you suspect the product is not working properly or if you have any questions about your product, contact your Fuji Electric representative. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
For an inverter with an output circuit filter installed, the total secondary wiring length should be 400 m (1312 ft) or less. If further longer secondary wiring is required, consult your Fuji Electric representative. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
Chapter 2 MOUNTING AND WIRING THE INVERTER 2.1 Installing the Inverter (1) Mounting base Install the inverter on a base made of metal or other non-flammable material. Do not mount the inverter upside down or horizontally. (2) Clearances Ensure that the minimum clearances indicated in Figure 2.1 and Table 2.1 are maintained at all times.
Page 85
- The wiring plate can be removed even with the front cover being mounted. - To expose the control printed circuit board (control PCB), remove the front cover. (2) 200V class series 55 to 90 kW (75 to 125HP) and 400V class series 110 to 710 kW (150 to 1000HP) Loosen the screws on the front cover, hold the right and left ends of the front cover, and slide it up to remove it.
Page 86
If it is difficult to punch semi-perforated sections out of the wiring plate Apply a rod with a sharp tip (e.g., chisel) to point "A" shown below and tap it using a hammer. Hammer or the like Connections "A" Chisel or the like Block or the like Wiring plate...
Page 87
(4) Wiring the main circuit power input wires For 200V class series inverters of 5.5 to 45 kW (7 to 60HP) and 400V ones of 11 to 90 kW (15 to 125HP), follow the wiring procedure given below for smooth wiring. Remove the screws and press the ends of the ferrite core support inwards to release the ferrite core from the main circuit terminal block.
2.2.2 Recommended wire sizes For the recommended wire sizes for the main circuits, refer to the "Conformity to the Low Voltage Directive in the EU" and "Conformity with UL standards and CSA standards (cUL-listed for Canada)" given in Preface. Crimp-style terminals for the main circuits should have insulation, insulation tubes, or similar treatment. 2.2.3 Terminal arrangement diagrams and screw specifications The tables and figures given below show the screw specifications and terminal arrangement diagrams.
Page 89
Table 2.2-1 Main Circuit Terminals(kW rating) (Continued) Aux main Aux. control Main circuit Grounding power supply power supply terminals terminals [R0, T0] [R1, T1] Nominal Power supply applied motor Inverter type Refer to: voltage (kW) Tightening Tightening Tightening Tightening Screw Screw Screw Screw...
Page 90
Table 2.2-2 Main Circuit Terminals(HP rating) Aux main Aux. control Main circuit Grounding power supply power supply terminals terminals [R0, T0] [R1, T1] Nominal Power supply applied motor Inverter type Refer to: voltage (HP) Tightening Tightening Tightening Tightening Screw Screw Screw Screw torque...
Page 91
Figure B Figure A : Do not connect. : Do not connect. Figure C Figure D : Do not connect. : Do not connect. Figure F Figure E Charge lamp (For Figure F) : Do not connect. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com...
Page 93
Figure K Charge lamp Arrow A Figure L (2) Arrangement of control circuit terminals Screw type of terminal block Europe type of terminal block (common to all inverter types) (common to all inverter types) Table 2.3 Control Circuit Terminals Screw specifications Wire strip length Terminal Recommended...
A DC link bus is connectable to these terminals. DC link bus terminals P(+), N(-) When you need to use the DC link bus terminals P(+) and N(-), consult your Fuji Electric representative. The three-phase input power lines are connected to these terminals. (*2) Main circuit power input...
Page 95
Wiring notes To make the machinery or equipment compliant with the EMC standards, wire the motor and inverter in accordance with the following. (*1) Use shielded wires for the motor cable and route the cable as short as possible. Firmly clamp the shield to the specified point inside the inverter.
Page 96
Table 2.5 Names, Symbols and Functions of the Control Circuit Terminals (Continued) Classifi- Name Symbol Functions cation Analog monitor [FM1] These terminals output monitor signals for analog DC voltage (0 to Analog [FM2] +10 V) or analog DC current (4 to 20 mA/0 to 20 mA). output Analog common [11]...
2.2.5 Connection diagrams [ 1 ] 200 V class series inverters of 45 kW (60HP) or below and 400 V ones of 90 kW (125HP) or below This section shows connection diagrams with the Enable input function used. SINK mode input by factory default Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com 2-13...
Page 99
[ 2 ] 200 V class series inverters of 55 kW (75HP)or above and 400 V ones of 110 kW (150HP)or above SINK mode input by factory default Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com 2-15...
Page 101
*1 Install a recommended molded case circuit breaker (MCCB) or residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with overcurrent protection function) in the primary circuit of the inverter to protect wiring. Ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity. *2 Install a magnetic contactor (MC) for each inverter to separate the inverter from the power supply, apart from the MCCB or RCD/ELCB, when necessary.
Page 102
400 V ones of 45 kW (60HP) or above) In its standard specifications, the FRENIC-HVAC supports DC power supply input. However, inverters with a capacity of 200 V class series inverters of 22 kW (30HP) or above and 400 V ones of 45 kW (60HP) or above have components that are driven internally by an AC power supply and therefore require a supply of AC power.
Page 103
(0H1) or charging circuit error (PbF). ・When using this product in combination with a PWM converter, refer to the instructions given in the FRENIC-HVAC User's Manual. Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com 2-19...
Page 104
Connector locations The switching connectors can be found in the following locations on the power supply printed circuit board: Separate power supply printed circuit board Supply voltage switching connector (CN UX) Main power supply switching connectors (CN R, CN W) Auxiliary main circuit power input terminals (R1, T1) Figure 2.5 Switching Connector Locations...
Page 105
Auxiliary control power input terminals (R0, T0) Main power supply switching connectors (CN R, CN W) Auxiliary main circuit power input terminals (R1, T1) Supply voltage switching connector (CN UX) Figure 2.7 Switching Connector Locations (400 V class series inverters of 160 kW (250HP) or above) To remove a connector, squeeze the top of the latch between your fingers to release the fastener and pull off the connector.
Note that the inverter with the keypad removed is rated IP00. For detailed instructions on how to mount the keypad on the panel, refer to the FRENIC-HVAC User’s Manual, Chapter 5, Section 5.2 "Mounting and Connecting a Keypad to the Panel."...
Chapter 3 NAMES AND FUNCTIONS OF KEYPAD COMPONENTS LED Indicators These indicators show the current running status of the inverter. STATUS (green): Running state WARN. (yellow): Light alarm state ALARM (red): Alarm (heavy alarm) state LCD Monitor This monitor shows the following various information about the inverter according to the operation modes.
Chapter 4 RUNNING THE MOTOR FOR A TEST 4.1 Checking Prior to Powering ON Check the following before powering on the inverter. (1) Check that the wiring is correct. Especially check the wiring to the inverter input terminals L1/R, L2/S and L3/T and output terminals U, V, and W.
Deceleration time 1 20.00 (s) (Note) For details about the configuration procedure of function codes, refer to the FRENIC-HVAC User's Manual, Chapter 5, Section 5.6.3.1 "Configuring function codes." 4.4 Running the Inverter for Motor Operation Check After completion of preparations for a test run as described above, start running the inverter for motor operation check using the following procedure.
Page 110
< Check points during a test run > • Check that the motor is running in the forward direction. • Check for smooth rotation without motor humming or excessive vibration. • Check for smooth acceleration and deceleration. When no abnormality is found, press the key again to start driving the motor, then increase the reference frequency using keys.
(3) Enable circuit (safety circuit) failure inverter is defective. detected Consult your Fuji Electric representative. (The alarm cannot be released.) 4.5 Preparation for Practical Operation After verifying normal motor running with the inverter in a test run, proceed to the practical operation.
Chapter 5 TROUBLESHOOTING 5.1 Alarm Codes Table 5.1 Quick List of Alarm Codes Code Name Description The inverter momentary output current exceeded the overcurrent level. Instantaneous overcurrent OC1: Overcurrent during acceleration OC2: Overcurrent during deceleration OC3: Overcurrent during running at a constant speed A ground-fault current flowed from the inverter’s output terminals.
Page 113
Table 5.1 Quick List of Alarm Codes(Continued) Code Name Description PID feedback error The PID feedback signal wire is broken under PID control. Current input break detection A break was detected in the current input. Enable circuit failure The Enable circuit was diagnosed as a circuit failure. A customizable logic configuration error has caused an Customizable logic error alarm.
Chapter 6 MAINTENANCE AND INSPECTION Perform daily and periodic inspections to avoid trouble and keep reliable operation of the inverter for a long time. 6.1 Daily Inspection Visually inspect the inverter for operation errors from the outside without removing the covers when the inverter is ON or operating.
These parts are likely to deteriorate with age due to their constitution and properties, leading to the decreased performance or failure of the inverter. When the replacement is necessary, consult your Fuji Electric representative. Table 6.2 Replacement Parts Standard replacement intervals (See Notes below.)
1) In the event that breakdown occurs during the product's warranty period which is the responsibility of Fuji Electric, Fuji Electric will replace or repair the part of the product that has broken down free of charge at the place where the product was purchased or where it was delivered. However, if the following cases are applicable, the terms of this warranty may not apply.
Page 117
The breakdown was caused by modifications or repairs affected by a party other than Fuji Electric. The breakdown was caused by improper maintenance or replacement using consumables, etc.
Chapter 7 SPECIFICATIONS 7.1 Standard Model Three-phase 200 V class series (kW rating) (0.75 to 90kW) Item Specifications Type 0.75 1.5 18.5 (FRN_ _ _AR1-2) (*1) (4.0) (*10) Nominal applied motor (kW) (*2) 0.75 1.5 18.5 (Rated output) (4.0) (*10) Rated capacity (kVA) (*3) Voltage (V) (*4) 3-phase, 200 to 240 V (with AVR function)
Page 119
(*10) 4.0 kW for the EU. (*11) Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] x 67 (See IEC/EN 61800-3.) If this value is 2 to 3%, use an optional AC reactor (ACR). *Applies to all models, regardless of capacity. Even if the voltage drops down to -20%, the inverter can run (operation guaranteed) provided that the load current is within the inverter rated current range.
Page 120
Three-phase 400 V class series(kW rating) (0.75 to 37 kW) Item Specifications Type 0.75 18.5 (*10) (FRN_ _ _AR1 -4 ) (*1) (4.0) Nominal applied motor (kW) (*2) 0.75 18.5 (*10) (4.0) (Rated output) Rated capacity (kVA) (*3) Voltage (V) (*4) 3-phase, 380 to 480 V (with AVR function) Rated current (A) (*5) 13.5...
Page 121
(45 to 710 kW) Item Specifications Type (FRN_ _ _AR1 -4 ) (*1) Nominal applied motor (kW) (*2) (Rated output) Rated capacity (kVA) (*3) 114 134 891 1044 Voltage (V) (*4) 3-phase, 380 to 480 V (with AVR function) Rated current (A) (*5) 112 150 176 960 1170 1370 Overload capability...
Page 122
Three-phase 230 V class series(HP rating) (001 to 125 HP) Item Specifications Type (FRN_ _ _AR1 -2U) (*1) Nominal Three phase AC208V applied input motor motor [HP] AC230 (*2) motor (Rated Single phase AC208V output) input motor AC230 motor Three Rated capacity (kVA) phase (*3)
Page 123
(*1) A box ( ) replaces an alphabetic letter depending on the enclosure. Enclosure: M (IP21), L (IP55) or S (IP00) (*2) US 4-pole standard induction motor. (*3) Rated capacity is calculated by assuming the output rated voltage as 230 V. (*4) Output voltage cannot exceed the power supply voltage.
Page 124
Three-phase 460 V class series(HP rating) (001 to 075 HP) Item Specifications Type (FRN_ _ _AR1 -4U) (*1) Nominal applied Three AC460V motor [HP] (*2) phase input motor (Rated output) Single phase input Three Rated capacity (kVA) phase input (*3) Rated current (A) 13.5 18.5...
Page 125
(100 to 1000 HP) Item Specifications Type 1000 (FRN_ _ _AR1 -4U) (*1) Nominal Three AC460V 1000 applied motor phase input motor (HP) (*2) Single (Rated output) phase input Three Rated capacity (kVA) 1091 phase (*3) input Rated current (A) 1170 1370 Single Rated capacity (kVA)
Page 126
(*8) EMC filters and DCR does not conform to each corresponding standards when single phase input use. (*9) Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] x 67 (See IEC/EN 61800-3.) If this value is 2 to 3%, use an optional AC reactor (ACR). (*10) It is applicable when the power supply is supplied from 3-phase 200V series transformer which is through 3-phase 400V series transformer.
By installing an external EMC-compatible filter to the input side of 200 V series 55kW (75HP) or above inverters, the EMC directive emission category can be changed from C3 to C2. Refer to "11.1 European Standards Compliance" in Chapter 11 of the FRENIC-HVAC User's Manual for details if installing an external EMC-compatible filter.
Compliance with EMC Standards 8.3.1 General The CE marking on inverters does not ensure that the entire equipment including our CE-marked products is compliant with the EMC Directive. Therefore, CE marking for the equipment shall be the responsibility of the equipment manufacturer.
Clamp for control signal lines Figure 8.2 Wiring to Control Circuit Terminals 5) When using an externally connected EMC filter (optional), place the inverter and filter on a grounded metal plate such as the surface of a panel, as shown in Figure 8.3. If noise emissions exceed the standard, place the inverter and any peripheral equipment inside a metal panel.
Page 135
Table 8.3 Inverter Leakage Current Leakage Leakage Input power Inverter type Input power Inverter type current (mA) current (mA) FRN0.75AR1 -2 FRN0.75AR1 -4 FRN001AR1 -2U FRN001AR1 -4U FRN1.5AR1 -2 FRN1.5AR1 -4 FRN002AR1 -2U FRN002AR1 -4U FRN2.2AR1 -2 FRN2.2AR1 -4 FRN003AR1 -2U FRN003AR1 -4U FRN3.7AR1 -2 FRN3.7AR1 -4...
Page 136
Table 8.4 EMC Filter (Optional) Use and Leakage Currents EMC filter leakage Input power Inverter type Filter model current (mA) FRN55AR1S-2 FRN075AR1S-2U FRN75AR1S-2 Three-phase FS5536-400-99-1 200 V FRN100AR1S-2U FRN90AR1S-2 FRN125AR1S-2U FRN110AR1S-4 FRN150AR1S-4U FS5536-250-99-1 FRN132AR1S-4 FRN200AR1S-4U FRN160AR1S-4 FRN250AR1S-4U FRN200AR1S-4 FS5536-400-99-1 FRN300AR1S-4U FRN220AR1S-4 FRN350AR1S-4U FRN280AR1S-4...
8.5.2 Considerations when using FRENIC-HVAC in systems to be certified by UL and cUL If you want to use the FRENIC-HVAC series of inverters as a part of UL Standards or CSA Standards (cUL certified) certified product, refer to the related guidelines described on pages xi to xx.
Page 139
In no event will Fuji Electric Co., Ltd. be liable for any direct or indirect damages resulting from the application of the information in this manual.