C22 to C28
Pattern Operation (Stages 1 to 7)
C22 to C28 configure stages 1 to 7, respectively, by setting the run time, motor rotation
direction and acceleration/deceleration time for each stage.
The inverter runs in the order of stages 1 to 7 (in the order of C22 to C28).
Items to be Configured
for Each Stage
Run time
Motor rotation direction
Acceleration/deceleration time
( * ) The number of significant figures for the run time is 3. Upper three digits can be set.
Example: 100 F 3
Setting the run time at "0.00 s" skips the corresponding stage to the next one.
Reference frequencies to be applied in a pattern operation are multistep frequencies 1 to 7
(C05 to C11) assigned to stages 1 to 7, respectively, as listed below. Specify multistep
frequencies with C05 to C11.
Stage No.
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
Stage 7
0.00 to 6000.00 s ( * )
FWD: Forward direction (clockwise)
REV: Reverse direction (counterclockwise)
1: F07 (Acceleration time 1), F08 (Deceleration time 1)
2: E10 (Acceleration time 2), E11 (Deceleration time 2)
3: E12 (Acceleration time 3), E13 (Deceleration time 3)
4: E14 (Acceleration time 4), E15 (Deceleration time 4)
Acceleration/deceleration time:
Acceleration time 3, Deceleration time 3
Motor rotation direction:
Forward direction (counterclockwise)
Run time: 100 s
Reference frequency
C05 (Multistep frequency 1)
C06 (Multistep frequency 2)
C07 (Multistep frequency 3)
C08 (Multistep frequency 4)
C09 (Multistep frequency 5)
C10 (Multistep frequency 6)
C11 (Multistep frequency 7)
6-128