J103
PID Control 1 (Feedback selection)
Select a feedback value for PID controls 1 and 2.
- Data setting range: 1 to 14
Data for J103 Data for J203
1
--
10
11
12
13
14
PID control 1 feedback selection block diagram
PID1
Feedback value
PID control 2
Feedback value
PID control 2 feedback selection block diagram
PID 1
Feedback value
PID 2
Feedback value
1
PID control 1 feedback value
2
PID control 2 feedback value
--
Addition (PID control 1 feedback value + PID control 2 feedback
value)
--
Difference (PID control 1 feedback value - PID control 2
feedback value)
--
Average ((PID control 1 feedback value + PID control 2 feedback
value) / 2)
13
Maximum (Use larger of PID control 1 or 2 feedback values)
--
Minimum (Use smaller of PID control 1 or 2 feedback values)
1
10
Addition
11
Difference
12
Average
13
Selection of
maximum
14
Selection of
minimum
1
2
13
Max
selection