Command sources specified by y98 (Bus link function, Mode selection)
Data for y98
Frequency command
0
Follow H30 data
1
Via fieldbus (option)
2
Follow H30 data
3
Via fieldbus (option)
Combination of command sources
Inverter itself
Via RS-485
communications
link (port 1)
Via RS-485
communications
link (port 2)
Via fieldbus
H30 = 0 (2 or 6)
(option)
y98 = 2
 For details, refer to the RS-485 Communication User's Manual or the Field Bus Option
Instruction Manual.
• When the terminal command LE ("Enable communications link via RS-485 or fieldbus") is
assigned to a digital input terminal, turning LE ON makes the settings of H30 and y98
enabled. When LE is OFF, those settings are disabled so that both frequency commands
and run commands specified from the inverter itself take control.
(Refer to the descriptions of E01 through E07, data = 24.)
No LE assignment is functionally equivalent to the LE being ON.
Frequency command
Via RS-485
Inverter itself
communications
link (port 1)
H30 = 0
H30 = 1
y98 = 0
y98 = 0
H30 = 2
H30 = 3
y98 = 0
y98 = 0
H30 = 6
H30 = 7
y98 = 0
y98 = 0
H30 = 1 (3 or 7)
y98 = 2
6-154
Run command
Follow H30 data
Follow H30 data
Via fieldbus (option)
Via fieldbus (option)
Via RS-485
Via fieldbus
communications
(option)
link (port 2)
H30=4
H30=0 (1 or 4)
y98=0
y98=1
H30=2 (3 or 5)
H30=5
y98=1
y98=0
H30=8
H30=6 (7 or 8)
y98=0
y98=1
H30 = 4 (5 or 8)
H30 = 0 (1 to 8)
y98 = 2
y98 = 3