Fuji Electric FRENIC-HVAC User Manual page 384

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

F32, F34,
Pulse Output [FM2] (Mode selection, Voltage adjustment, Function)
F35
These function codes allow terminal [FM2] to output monitored data such as the output
frequency and the output current in an analog DC voltage or current. The magnitude of such
analog voltage or current is adjustable.
Mode selection (F32)
F29 specifies the output form of the terminal [FM2]. You need to set switch SW6 on the
control printed circuit board (control PCB).
For details of the slide switches on the control PCB, refer to Chapter 2
"SPECIFICATIONS."
Data for F32
0
1
2
The output current is not isolated from analog input, and does not have an isolated
power supply. Therefore, if an electrical potential relationship between the inverter
and peripheral equipment has been established, e.g., by connecting an analog,
cascade connection of a current output device is not available.
Keep the connection wire length as short as possible.
Voltage adjustment (F34)
F34 allows you to adjust the output voltage within the range of 0 to 300%.
Function (F35)
F35 specifies what is output to analog output terminal [FM2]. The monitor objects are the
same as for F31. Refer to the description of F31.
[FM2] output form
Voltage (0 to +10 VDC)
Current (4 to +20 mA DC)
Current (0 to +20 mA DC)
6-74
Position of slide switch SW6
mounted on the control PCB
VO2
IO2
IO2