H96
STOP Key Priority/Start Check Function
H96 specifies a functional combination of "STOP key priority" and "Start check function" as
listed below.
Data for H96
0
1
2
3
STOP key priority
Even when a run command is entered from a digital input terminal or via the RS-485
communications link (link operation), pressing the
stop the motor. After that, an Er6 alarm occurs.
Start check function
For safety, this function checks whether any run command has been turned ON or not in each
of the following situations. If any has been turned ON, the inverter does not start up with
alarm code Er6 displayed.
• When the power to the inverter is turned ON.
• When the
command RST ("Reset alarm") is turned ON.
• When the run command source is switched by a digital input terminal command such as LE
("Enable communications link via RS-485 or fieldbus") or LOC ("Select local (keypad)
operation").
H97
Clear Alarm Data
H97 clears alarm data (alarm history and relevant information) stored in the inverter. To clear
alarm data, simultaneous keying of "
Data for H97
0
1
STOP key priority
Disable
Enable
Disable
Enable
key is pressed to release an alarm status or when the digital input terminal
key +
Disable
Enable
(Setting "1" clears alarm data and then returns to "0.")
6-170
Start check function
Disable
Disable
Enable
Enable
key forces the inverter to decelerate to
H45 (Mock Alarm)
key" is required.
Function