Nominal
Power
applied
supply
Inverter type
motor
voltage
(HP)
1
FRN001AR1-2U
2
FRN002AR1-2U
3
FRN003AR1-2U
5
FRN005AR1-2U
7.5
FRN007AR1-2U
10
FRN010AR1-2U
15
FRN015AR1-2U
Three-
20
FRN020AR1-2U
phase
25
FRN025AR1-2U
230 V
30
FRN030AR1-2U
40
FRN040AR1-2U
50
FRN050AR1-2U
60
FRN060AR1-2U
75
FRN075AR1S-2U
100
FRN100AR1S-2U
125
FRN125AR1S-2U
Note 1: A box () replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
Note 2: Generated losses listed in the above table are approximate values that are calculated according to the
following conditions:
- The power supply is three-phase 200 V 50 Hz with 0% interphase voltage unbalance ratio.
- The power supply capacity uses the larger of either 500 kVA or 10 times the rated capacity of the
inverter.
- The motor is a 4-pole standard model at full load (100%).
Table 4.5 AC Reactor (ACR) Specifications
AC reactor
Rated
type
current (A)
ACR2-0.75A
5
ACR2-1.5A
8
ACR2-2.2A
11
ACR2-3.7A
17
ACR2-5.5A
25
ACR2-7.5A
33
ACR2-11A
46
ACR2-15A
59
ACR2-18.5A
74
ACR2-22A
87
ACR2-37
200
ACR2-37
200
ACR2-55
270
ACR2-55
270
ACR2-75
390
ACR2-90
450
4-37
Reactance
Coil
(mΩ/phase)
resistance
(mΩ)
50 Hz
60 Hz
493
592
-
295
354
-
213
256
-
218
153
-
87.7
105
-
65
78
-
45.5
54.7
-
34.8
41.8
-
28.6
34.3
-
24
28.8
-
10.8
13
0.5
10.8
13
0.5
7.5
9
0.375
7.5
9
0.375
5.45
6.54
0.25
4.73
5.67
0.198
4.4 Options
Generated
loss (W)
12
14
16
23
27
30
37
43
51
57
28.6
40.8
47.1
66.1
55.1
61.5