Code
Name
E98
Terminal [FWD] Function
E99
Terminal [REV] Function
Available in the ROM version 1500 or later.
Data setting range
Selecting function code data assigns the corresponding function
to terminals [FWD] and [REV] as listed below.
0 (1000):
Select multistep frequency (0 to 1 steps)
1 (1001):
Select multistep frequency (0 to 3 steps)
2 (1002):
Select multistep frequency (0 to 7 steps)
3 (1003):
Select multistep frequency (0 to 15 steps)
4 (1004):
Select ACC/DEC time (2 steps)
5 (1005):
Select ACC/DEC time (4 steps)
6 (1006):
Enable 3-wire operation
7 (1007):
Coast to a stop
8 (1008):
Reset alarm
9 (1009):
Enable external alarm trip
(9 = Active OFF, 1009 = Active ON)
11 (1011):
Select frequency command 2/1
13:
Enable DC braking
14 (1014):
Select torque limiter level 2/1
15:
Switch to commercial power (50 Hz)
16:
Switch to commercial power (60 Hz)
17 (1017):
UP (Increase output frequency)
18 (1018):
DOWN (Decrease output frequency)
19 (1019):
Enable data change with keypad
20 (1020):
Cancel PID control
21 (1021):
Switch normal/inverse operation
22 (1022):
Interlock
24 (1024):
Enable communications link via RS-485
or fieldbus
25 (1025):
Universal DI
26 (1026):
Enable auto search for idling motor
speed at starting
30 (1030):
Force to stop
(30 = Active OFF, 1030 = Active ON)
33 (1033):
Reset PID integral and differential
components
34 (1034):
Hold PID integral component
35 (1035):
Select local (keypad) operation
38 (1038):
Enable run commands
39:
Protect motor from dew condensation
40:
Enable integrated sequence to switch
to commercial power (50 Hz)
41:
Enable integrated sequence to switch
to commercial power (60 Hz)
58 (1058):
Reset UP/DOWN frequency
72 (1072):
Count the run time of commercial
power-driven motor 1
80 (1080):
Cancel customizable logic
81 (1081):
Clear all customizable logic timers
87 (1087):
Run command 2/1
88:
Run forward 2
89:
Run reverse 2
98:
Run forward
99:
Run reverse
100:
No function assigned
131 (1131): Flowrate switch
132 (1132): Filter clogging reverse rotation command
133 (1133): Switch PID channel
134:
Switch to fire mode
171 (1171): PID multistep command
172 (1172): PID multistep command
181 (1181): External PID multistep command
182 (1182): External PID multistep command
190 (1190): Cancel timer
191 (1191): Enable timer 1
192 (1192): Enable timer 2
193 (1193): Enable timer 3
194 (1194): Enable timer 4
201 (1201): External PID control 1 ON command
202 (1202): Cancel external PID control 1
203 (1203): Switch normal/inverse operation
under external PID control 1
204 (1204): Reset external PID1 integral and
differential components
205 (1205): Hold external PID1 integral component
6-8
Change
Data
Default
when
copying
running
(SS1)
N
Y
(SS2)
N
Y
(SS4)
(SS8)
(RT1)
(RT2)
(HLD)
(BX)
(RST)
(THR)
(Hz2/Hz1)
(DCBRK)
(TL2/TL1)
(SW50)
(SW60)
(UP)
(DOWN)
(WE-KP)
(Hz/PID)
(IVS)
(IL)
(LE)
(U-DI)
(STM)
(STOP)
(PID-RST)
(PID-HLD)
(LOC)
(RE)
(DWP)
(ISW50)
(ISW60)
(STZ)
(CRUN-M1)
(CLC)
(CLTC)
(FR2/FR1)
(FWD2)
(REV2)
(FWD)
(REV)
(NONE)
(FS)
(FRC)
(PID2/1)
(FMS)
(PID-SS1)
(PID-SS2)
(EPID-SS1)
(EPID-SS2)
(TMC)
(TM1)
(TM2)
(TM3)
(TM4)
(EPID1-ON)
(%/EPID1)
(EPID1-IVS)
(EPID1-RST)
(EPID1-HLD)
Related
setting
page
6-124
98
99

Hide quick links:

Advertisement

Table of Contents
loading