Table 4.1 Currents Flowing through Inverter (continued)
Nominal applied
Power supply
motor
voltage
(HP)
10
15
20
25
30
Three-phase
575 V
40
50
60
75
100
125
150
200
250
300
Note: A box () replaces an alphabetic letter depending on the enclosure.
M (NEMA/UL TYPE 1) or L (NEMA/UL TYPE 12)
Note: The input RMS current values listed in the above table apply when the inverter is connected with a power
supply of 575 V, 60 Hz, Rsce = 120.
Inverter type
1
FRN001AR1-5U
2
FRN002AR1-5U
3
FRN003AR1-5U
5
FRN005AR1-5U
7.5
FRN007AR1-5U
FRN010AR1-5U
FRN015AR1-5U
FRN020AR1-5U
FRN025AR1-5U
FRN030AR1-5U
FRN040AR1-5U
FRN050AR1-5U
FRN060AR1-5U
FRN075AR1-5U
FRN100AR1-5U
FRN125AR1-5U
FRN150AR1-5U
FRN200AR1S-5U
FRN250AR1S-5U
FRN300AR1S-5U
4-4
575 V, 60 Hz
Input RMS current
DC link bus current
(A)
1.2
2.1
3.0
5.2
7.2
9.7
14.4
19.5
24.0
28.6
38.8
48.3
57.9
71.0
94.7
113
140
199
249
272
(A)
1.5
2.6
3.7
6.4
8.8
12
18
24
29
35
48
59
71
87
116
138
172
244
305
333