Run forward 2 -- FWD2 (Function code data = 88)
Turning the FWD2 ON runs the motor in the forward direction; turning it OFF decelerates it
to a stop.
The FWD2 can be assigned by any of E01 to E07, E98 and E99.
Run reverse 2 -- REV2 (Function code data = 89)
Turning the REV2 ON runs the motor in the reverse direction; turning it OFF decelerates it to
a stop.
The REV2 can be assigned by any of E01 to E07, E98 and E99.
Run forward -- FWD (Function code data = 98)
Turning the FWD ON runs the motor in the forward direction; turning it OFF decelerates it to
a stop.
The FWD can be assigned by E98 or E99 only.
Run reverse -- REV (Function code data = 99)
Turning the REV ON runs the motor in the reverse direction; turning it OFF decelerates it to
a stop.
The REV can be assigned by E98 or E99 only.
No function assigned (Function code data = 100)
Use this when no function is to be assigned to general-purpose, digital input terminals or the
customizable logic function disables terminal functions.
Flowrate switch -- FS (Function code data = 131)
Turning the FS ON uses the flowrate sensor as a flowrate switch for detecting the dry pump
or the end of curve.
Refer to J163 through J166.
Filter clogging reverse rotation command -- FRC (Function code data = 132)
Turning the FRC ON activates the filter clogging prevention to run the motor in the forward
and reverse directions repeatedly according to the reverse rotation running time (J194).
Refer to J188 through J196.
Switch PID channel -- PID2/1 (Function code data = 133)
The PID2/1 switches between PID control 1 (J101 through J131) and PID control 2 (J201
through J231).
Refer to J101 through J131 and J201 through J231.
Switch to fire mode -- FMS (Function code data = 134)
Turning the FMS this terminal command ON switches to the fire mode to be used in an
emergency, in which the inverter runs the motor at the predetermined speed.
Refer to H116 through H121.
6.3 Details of Function Codes
6-101