Fuji Electric FRENIC-HVAC User Manual page 331

Frenic-hvac series
Hide thumbs Also See for FRENIC-HVAC:
Table of Contents

Advertisement

Code
Name
J510 External PID Control 1
J511
I (Integral time) 0.0 to 3600.0 s
J512
D (Differential time) 0.00 to 600.00 s
J513
(Feedback filter) 0.0 to 900.0 s
J514
(Anti-reset wind-up) OFF: Disable
J515
(ON/OFF control hysteresis width) 0.00 to 9990.00
J516
(Proportional operation output convergent
J517
(Proportional cycle) 1 to 150 s
J518
(Upper limit of PID process output) -10 to +110%
J519
(Lower limit of PID process output) -10 to +110%
J520
(Upper and lower limits) 0: Limit PID output with J518, J519
J521
(Alarm output selection) 0: Absolute-value alarm (PV)
J522
(Upper level alarm (AH)) OFF: Disable
J524
(Lower level alarm (AL)) OFF: Disable
J527
(Feedback error detection mode) 0: Disable (Turns ON output signals (EPV1-ERR) and continues
J529
(Feedback error upper-limit)
J530
(Feedback error lower-limit) Auto: -5% equivalent
J531
(Feedback error detection time) 0.0 to 300.0 s
J540
(Manual command) 0: Keypad ( /
J550 External PID Multistep Command
(Mode selection)
J551
(Multistep command 1) -999.00 to 0.00 to 9990.00
J552
(Multistep command 2) -999.00 to 0.00 to 9990.00
J553
(Multistep command 3) -999.00 to 0.00 to 9990.00
*6 The upper and lower level values are restricted by the maximum and minimum scales.
Data setting range
P (Gain) ON/OFF: ON/OFF control
0.000 to 30.000 times
0.00 to 9990.00
*6
*6
0 to 150%
value)
1: 110%, -10% of PID output with J518 exceeded or less than
J519
1: Absolute-value alarm (PV) (with Hold)
2: Absolute-value alarm (PV) (with Latch)
3: Absolute-value alarm (PV) (with Hold and Latch)
4: Deviation alarm (PV)
5: Deviation alarm (PV) (with Hold)
6: Deviation alarm (PV) (with Latch)
7: Deviation alarm (PV) (with Hold and Latch
8: Absolute-value alarm (SV)
9: Absolute-value alarm (SV) (with Hold)
10: Absolute-value alarm (SV) (with Latch)
11: Absolute-value alarm (SV) (with Hold and Latch)
12: Absolute-value alarm (MV)
13: Absolute-value alarm (MV) (with Hold)
14: Absolute-value alarm (MV) (with Latch)
15: Absolute-value alarm (MV) (with Hold and Latch)
-999.00 to 0.00 to 9990.00
*6
-999.00 to 0.00 to 9990.00
*6
operation.)
1: Enable (Free run stop (PVA trip))
2: Enable (Deceleration and stop (PVA trip))
Auto: 105% equivalent
-999.00 to 0.00 to 9990.00
*6
-999.00 to 0.00 to 9990.00
*6
key)
8: Keypad ( /
key) (Balanceless-bumpless)
51: External PID command 1 (Analog input: Terminals [12], [C1]
and [V2])
Bit 0: Enable multistep command under external PID control 1
Bit 1: Enable multistep command under external PID control 2
Bit 2: Enable multistep command under external PID control 3
6-21
6.2 Function Code Tables
Change
Data
Default
Related
when
copying
setting
page
running
Y
Y
0.100
6-229
Y
Y
0.0
Y
Y
0.00
Y
Y
0.5
Y
Y
OFF
6-233
Y
Y
0.00
6-234
Y
Y
0
6-235
Y
Y
30
6-236
Y
Y
100
6-237
Y
Y
0
Y
Y
0
Y
Y
0
6-238
Y
Y
OFF
Y
Y
OFF
Y
Y
0
6-241
Y
Y
Auto
Y
Y
Auto
Y
Y
0.1
N
Y
0
6-243
N
Y
0
6-244
Y
Y
0.00
Y
Y
0.00
Y
Y
0.00

Hide quick links: